BS 5308 Cables

BS 5467 Cables

BS 5467 Armoured Power Cables, 1900/3300V

Single-core 1900/3300 V cables with solid aluminum conductor

Application

BS 5467 Cables are used for power and control circuits, they can offer excellent protection through the use of a

heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for

direct burial in the ground.

Construction

Conductor :Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228.

Insulation Colour Code :XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6)

1 Core : Brown   

3 Cores: Brown, Black, Grey

Bedding Armour Outer Sheath :extruded layer of polymeric material

Technical Information

Voltage rating 1900/3300V

Temperature rating 0°C to +90°C

Bending radius 1.5mm² to 16mm²: 6 x overall diameter

                          25mm² and above: 8 x overall diameter

Flame retardant IEC60332 part 1, BS4066 part 1

BS 5467 Armoured Power Cables, 1900/3300V

Nominal Cross-sectional Area Nominal Insulation thickness Nominal beddingthickness Nominal Alum Wire Armor dia. Nominal Sheath thickness Approx.Overall Diameter AprroxWeight
mm² mm mm mm mm mm kg/km
1x50 2 0.8 1.25 1.6 19.4 600
1x70 2 0.8 1.25 1.6 20.9 710
1x95 2 0.8 1.25 1.6 22.5 810
1x120 2 1 1.6 1.7 25.2 1065
1x150 2 1 1.6 1.7 26.5 1210
1x185 2 1 1.6 1.8 28.3 1390
1x240 2 1 1.6 1.8 30.5 1630
1x300 2 1 1.6 1.9 32.8 1900