EN50288-7 Cables
XLPE Insulated, LSZH Sheathed Instrumentation Cables

EN 50288-7 Cables

APPLICATION

EN 50288-7 unarmoured LSZH sheathed cables are generally use for indoor installation and suitable for wet and

damp areas.Generally, EN 50288-7cables are used within industrial process manufacturing plants for

communication, data and voice transmission signals and services. Also used for the interconnection of electrical

equipment and instruments, the LSZH sheath can reduce toxic smoke and fume emission.

STANDARDS

RE-2Y(St)YSWAY 70°C / 300 V

Basic design to EN 50288-7

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile

strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING

300V

CABLE CONSTRUCTION

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm

Binder tape: PETP transparent tape

Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with

tinned copper drain wire, 0.5mm²

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti

rodent andanti termite properties can be offered as option.

COLOUR CODE

Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.

Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +90°C

Temperature Range During Installation (Mobile State): -5°C – +50°C

Minimum Bending Radius:7.5 X Overall Diameter

Electrical PROPERTIES

Conductor Area Size mm² 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C)  Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
  ≤ 4 pairs 90 90 90 102 102
  all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500

CONSTRUCTION PARAMETERS

 

 

Caledonian Cable Code

RE-2X(St)H

 

No. of Pairs x2xCross Section

 

Nominal Insulation Thickness

 

Nominal Outer Sheath Thickness

 

Nominal Overall Diameter

 

Approx. Weight

 

No.x2xmm2

mm

mm

mm

kg/km

RE-2X(St)H 1P0.5

1x2x0.50

0.35

0.8

5.2

38

RE-2X(St)H 1P0.75

1x2x0.75

0.38

0.8

5.6

49

RE-2X(St)H 1P1.0

1x2x1.0

0.40

0.9

6.3

56

RE-2X(St)H 1P1.3

1x2x1.3

0.45

0.9

6.8

65

RE-2X(St)H 1P1.5

1x2x1.5

0.45

0.9

7.1

71

Note : Other conductor sizes & core configurations are available upon request.