Home
Over ons
Produkten
Downloaden
Technische Lib
Contact
Navraag
Sitemap
Links
 

Alarm & Audio & Elektronische Kabel

Belden gelijkwaardige kabels

Coax Kabels

Control Kabels

Fiber Optic Kabels

Flexibele Kabels

Instrumentatie Kabel

Lan kabels
Energie Kabel
Spoorweg Kabel

Robotica

Rollend materieel kabels
Rubber & Crane kabels
Beveiliging kabels

Telefoonkabels

Luchthaven Kabels

Bus kabels

Kabel Klieren

Data Kabels

Hitte detectie kabels
Hoge temperatuur kabels
Kabels snelweg
Marine, olie-, gas-en petrochemische Kabels
Speciaal Kabels
Spiraal Kabels
Thermokoppel Kabels
Mining Cables
Industrial Cables
Undersea Cables
Military Cables
Marine Cables
Hoop-Up Wire
Other Cables
     
  Indoor tight buffer fiber optic cable  
Indoor Used Tight Buffered Fiber
Optical Cable
outdoor multi loose tube fiber optic cable
Outdoor Used Multi Loose Tube
Fiber Optical Cable
 
  Marine Cable  

Marine Cable

P6 or P6/P13 BFOU 3.6/6kV

Applications :

  • These cables are fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

Standards :

  • IEC 60092-353 IEC 60092-351
    IEC 60092-359 IEC 60332-1
    IEC 60332-3-22 IEC 60754-1,2
    IEC 61034-1,2 NEK 606:2004
 

 

Construction :

  • Conductors :Circular tinned annealed stranded compacted copper to IEC 60228 class 2.
  • Conductor Screen : Semi conducting material.
  • Insulation : Mica tape + Halogen free EPR.
  • Insulation Screen : Semi conducting material and tinned copper wire braid.
  • Bedding : Halogen free compound.
  • Armour : Tinned copper wire braid.
  • Outer Sheath : Halogen free thermosetting compound, SHF2 (for TYPE P6), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P6/P13), coloured red.

Electrical Characteristics :

  • Nominal Cross Section Area mm² 25 35 50 70 95 120 150
    Nominal Conductor Diameter mm 6.5 7.4 8.7 10.3 12.2 13.8 15.1
    Maximum DC Resistant@20℃ Ω/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126
    Continuous Current Rating@45℃1 Core A 127 157 196 242 293 339 389
    Continuous Current Rating@45℃3 Core A 89 110 137 169 205 237 272
    Short Circuit Current 1s A 3580 5010 7150 10020 13590 17170 21460
    Operating Voltage KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6
  • Nominal Cross Section Area mm² 185 240 300 400 500 630
    Nominal Conductor Diameter mm 17.0 19.6 21.9 24.5 27.5 32.3
    Maximum DC Resistant@20℃ Ω/km 0.1 0.0762 0.0607 0.0475 0.0369 0.0286
    Continuous Current Rating@45℃1 Core A 444 522 601 690 780 890
    Continuous Current Rating@45℃3 Core A 311 365 421 483 546 623
    Short Circuit Current 1s A 26470 34340 42930 57230 71540 90140
    Operating Voltage KV 3.6/6 3.6/6 3.6/6 8.7/15 8.7/15 8.7/15

Ambient Temperature Correction Factors :

  • Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
    Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties :

  • Bending Radius :15×OD (during installation); 9×OD (fixed installed).
  • Temperature Range : -20℃ ~ +90℃.

Dimensions and Weight :

Construction No. of cores×Cross section
(mm²)
Nominal Insulation Thickness
mm
Nominal Sheath Thickness
mm
Nominal Overall Diameter
mm
Nominal Weight
kg/km
Inner Outer
1×16 2.5 1.5 1.2 24.8 950
1×25 2.5 1.6 1.2 26.3 1110
1×35 2.5 1.6 1.2 27.6 1260
1×50 2.5 1.7 1.3 29.1 1460
1×70 2.5 1.7 1.3 30.9 1740
1×95 2.5 1.8 1.4 33.2 2110
1×120 2.5 1.9 1.4 34.9 2430
1×150 2.5 1.9 1.4 36.9 2890
1×185 2.5 2.0 1.5 39.1 3370
1×240 2.6 2.1 1.6 42.2 4100
1×300 2.8 2.2 1.6 44.7 4810
1×400 3.0 2.3 1.7 48.1 5810
1×500 3.2 2.5 1.8 52.1 7030
1×630 3.2 2.6 1.9 56.5 8630
3×16 2.5 2.3 1.7 48.2 3550
3×25 2.5 2.5 1.8 51.5 4180
3×35 2.5 2.6 1.9 54.7 4820
3×50 2.5 2.7 1.9 57.4 5490
3×70 2.5 2.8 2.0 61.6 6590
3×95 2.5 3.0 2.1 66.2 7920
3×120 2.5 3.1 2.2 70.1 9150
3×150 2.5 3.3 2.3 74.0 10460
3×185 2.5 3.4 2.4 78.6 12010
3×240 2.6 3.7 2.6 86.3 14690
3×300 2.8 3.9 2.8 92.3 17130