IEC 60502-1 Cables  
600/1000V, PVC Insulated Cables 600/1000V, XLPE Insulated Cables

IEC 60502-1 Cables

600/1000V, XLPE Insulated Cables according to IEC 60502-1(armoured)

Application:

IEC 60502-1 cables are used for electricity supply in low voltage installation system, IEC 60502-1 cables are

suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations,

local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction:

Conductors:

Copper or Aluminium conductor, round standed or Shaped, Class 2 to IEC 60228, BS EN 60228. For smaller

sizes, a solid round conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.

Insulation:

XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90°C continuous operation.

Colour Code Colour Code (1) :
  1 Core : Red or Black
  2 Cores : Red, Black
  3 Cores : Red, Yellow, Blue
  4 Cores : Red, Yellow, Blue, Black
  5 Cores : Red, Yellow, Blue, Black, Green
  Above 5 Cores : Black Cores with White numerals
  Colour Code (2) :  
  1 Core : Brown or Blue
  2 Cores : Brown or Blue
  3 Cores : Brown, Black, Grey
  4 Cores : Blue, Brown, Black, Grey
  5 Cores : Green/Yellow, Blue, Brown, Black, Grey
  Above 5 Cores : Black Cores with White numerals

Assembly / Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers

Inner Sheath and the assembly is bedded with an extruded layer of PVC. In case of non-armoured cables, this

layer may be omitted Armour Aluminum/Galvanized Steel Wires applied helically over the bedding as per IEC

60502 or as per BS 5467, BS 6346. Single core cables shall be Aluminium wire armour. Aluminum/Steel Tapes

applied helically over the bedding of multi-core cables as per IEC 60502.

Outer Sheath Outer sheath shall be of Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.

Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight

resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as

LLDPE, MDPE, HDPE, LSF, CPE are available on request.

Fire Cables can be supplied with special flame retardant PVC outer sheath to comply with Performance the flame

test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, of Cable can also supply cables with

Low Smoke Halogen Free (LSHF) material according to IEC Sheaths 60502-1, BS 7211, BS 6724 or other

equivalent standards.

Cable Parameters:

Single core( aluminum wire armoured)

IEC 60502-1 Cables

Nominal Cross Section Diameter of Conductor (Approx.) Nominal Insulation thickness Nominal Inner Covering thickness Nominal Alum Wire dia. Nominal Sheath thickness Overall Diameter (Approx.)
mm² mm mm mm mm mm mm
1x4 2.3 0.7 1 0.8 1.8 10.9
1x6 2.8 0.7 1 0.8 1.8 11.4
1x10 3.6 0.7 1 0.8 1.8 12.2
1x16 4.5 0.7 1 0.8 1.8 13.1
1x25 5.6 0.9 1 0.8 1.8 14.6
1x35 6.7 0.9 1 1.25 1.8 16.6
1x50 8 1 1 1.25 1.8 18.1
1x70 9.4 1.1 1 1.25 1.8 19.7
1x95 11 1.1 1 1.6 1.8 22
1x120 12.4 1.2 1 1.6 1.8 23.6
1x150 13.8 1.4 1 1.6 1.8 25.4
1x185 15.3 1.6 1 1.6 1.8 27.4
1x240 17.5 1.7 1 1.6 1.9 29.9
1x300 19.5 1.8 1 2 2 33.1
1x400 22.6 2 1.2 2 2.2 37.3
1x500 25.2 2.2 1.2 2 2.3 40.5

Two cores(Galvanized steel wire armoured)

IEC 60502-1 Cables

Nominal Cross Section Diameter of Conductor (Approx.) Nominal Insulation thickness Nominal Inner Covering thickness Nominal Steel Wire dia. Nominal Sheath thickness Overall Diameter (Approx.)
mm² mm mm mm mm mm mm
2x1.5 1.4 0.7 1 0.8 1.8 12.8
2x2.5 1.8 0.7 1 0.8 1.8 13.6
2x4 2.3 0.7 1 0.8 1.8 14.6
2x6 2.8 0.7 1 1.25 1.8 16.5
2x10 3.6 0.7 1 1.25 1.8 18.1
2x16 4.5 0.7 1 1.25 1.8 19.9
2x25 5.6 0.9 1 1.6 1.8 23.6
2x35 6.7 0.9 1 1.6 1.8 25.8
2x50 8 1 1 1.6 1.9 29
2x70 9.4 1.1 1 2 2 33.2
2x95 11 1.1 1.2 2 2.1 37.1
2x120 12.4 1.2 1.2 2 2.3 40.5
2x150 13.8 1.4 1.2 2.5 2.4 45.4
2x185 15.3 1.6 1.4 2.5 2.6 49.9
2x240 17.5 1.7 1.4 2.5 2.7 55.1
2x300 19.5 1.8 1.6 2.5 2.9 60.2
2x400 22.6 2 1.6 2.5 3.1 67.7

Three cores(Galvanized steel wire armoured)

IEC 60502-1 Cables

Nominal Cross Section Diameter of Conductor (Approx.) Nominal Insulation thickness Nominal Inner Covering thickness Nominal Steel Wire dia. Nominal Sheath thickness Overall Diameter (Approx.)
mm² mm mm mm mm mm mm
3x1.5 1.4 0.7 1 0.8 1.8 13.2
3x2.5 1.8 0.7 1 0.8 1.8 14.1
3x4 2.3 0.7 1 0.8 1.8 15.2
3x6 2.8 0.7 1 1.25 1.8 17.1
3x10 3.6 0.7 1 1.25 1.8 18.9
3x16 4.5 0.7 1 1.25 1.8 20.8
3x25 5.6 0.9 1 1.6 1.8 24.7
3x35 6.7 0.9 1 1.6 1.8 27.2
3x50 8 1 1 1.6 1.9 30.6
3x70 9.4 1.1 1 2 2.1 35.2
3x95 11 1.1 1.2 2 2.2 39.3
3x120 12.4 1.2 1.2 2 2.3 43
3x150 13.8 1.4 1.4 2.5 2.5 48.6
3x185 15.3 1.6 1.4 2.5 2.7 53
3x240 17.5 1.7 1.4 2.5 2.8 58.5
3x300 19.5 1.8 1.6 2.5 3 64
3x400 22.6 2 1.6 3.15 3.3 73.5

Three cores+1(Galvanized steel wire armoured)

IEC 60502-1 Cables

Nominal Cross
Section
Diameter of Conductor (Approx.) Nominal Insulation thickness Nominal Inner Covering thickness Nominal Steel Wire dia. Nominal Sheath thickness Overall Diameter (Approx.)
mm² (3)
mm
(1)
mm
(3)
mm
(1)
mm
mm mm mm mm
3x 16/10 4.5 3.6 0.7 0.7 1 1.6 1.8 22.7
3x 25/16 5.6 4.5 0.9 0.7 1 1.6 1.8 26.5
3x 35/16 6.7 4.5 0.9 0.7 1 1.6 1.9 29
3x 50/25 8 5.6 1 0.9 1 1.6 2.1 33
3x 70/35 9.4 6.7 1.1 0.9 1.2 2 2.2 38
3x 95/50 11 8 1.1 1 1.2 2 2.3 42.4
3x120/70 12.4 9.4 1.2 1.1 1.2 2 2.5 48
3x150/70 13.8 9.4 1.4 1.1 1.4 2.5 2.7 52
3x185/95 15.3 11 1.6 1.1 1.4 2.5 2.8 57.2
3x240/120 17.5 12.4 1.7 1.2 1.6 2.5 3.1 64
3x300/150 19.5 13.8 1.8 1.4 1.6 2.5 3.2 69.8
3x400/185 22.6 15.3 2 1.6 1.6 3.15 3.6 78.6

Four cores(Galvanized steel wire armoured)

IEC 60502-1 Cables

Nominal Cross Section Diameter of Conductor (Approx.) Nominal Insulation thickness Nominal Inner Covering thickness Nominal Steel Wire dia. Nominal Sheath thickness Overall Diameter (Approx.)
mm² mm mm mm mm mm mm
4x1.5 1.4 0.7 1 0.8 1.8 14
4x2.5 1.8 0.7 1 0.8 1.8 14.9
4x4 2.3 0.7 1 1.25 1.8 17
4x6 2.8 0.7 1 1.25 1.8 18.2
4x10 3.6 0.7 1 1.25 1.8 20.2
4x16 4.5 0.7 1 1.6 1.8 23
4x25 5.6 0.9 1 1.6 1.8 26.7
4x35 6.7 0.9 1 1.6 1.9 29.5
4x50 8 1 1 2 2.1 34.2
4x70 9.4 1.1 1.2 2 2.2 38.8
4x95 11 1.1 1.2 2 2.3 42.9
4x120 12.4 1.2 1.4 2.5 2.5 48.6
4x150 13.8 1.4 1.4 2.5 2.7 53.2
4x185 15.3 1.6 1.4 2.5 2.8 58.1
4x240 17.5 1.7 1.6 2.5 3.1 64.8
4x300 19.5 1.8 1.6 2.5 3.2 70.4
4x400 22.6 2 1.8 3.15 3.6 81.3