EN50288-7 Cables | |||
XLPE Insulated, LSZH Sheathed Instrumentation Cables |
XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single Triple)
RE-2X(St)HSWAH 70°C / 300 V
APPLICATION:
EN 50288-7 cables are used for transmission of analoge and digital signals in instrument and control systems at
chemistry and petr°Chemistry industry plants, power plants, natural gas and petroluem plants, etc... EN 50288-
7 cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of
fire,EN 50288-7 cables inhibit the propagation of the flames whereby the development of smoke is extremely
low. EN 50288-7 Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g.
public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems.EN 50288-7 cables are
not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet l°Cations; on
racks, trays, in conduits.
STANDARDS
Basic design to EN50288-7
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance | ICEA S-73-532** |
Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile
strength/min.60% of elongation, *** denotes optional.
VOLTAGE RATING
300V
CABLE CONSTRUCTION
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.
Pair: Two conductors twisted to form a pair
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Overall Screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Inner sheath: HFFR compound, EN 50290-2-27
Armour: Galvenized round steel wire, EN 10257-1
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound
type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti
rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.
Outer Sheath: Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +70°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter
Electrical PROPERTIES
Conductor Area Size | mm² | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.35 | 0.38 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | |||||
Mutual Capacitance (1 kHz) | pF/m(Max.) | 115 | |||||
Capacitance unbalance(1 kHz) | pF/500 m (Max.) | 500 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Inductance | mH/km(Max.) | 1 | |||||
Operating voltage Urms | V | 300 | |||||
Test Voltage | Core to Core | V | 1500 | ||||
Core to Screen | V | 1500 |
CONSTRUCTION PARAMETERS
Caledonian Cable Code |
RE-2X(St)HSWAH |
|||||
No. of Triples x3xCross Section |
Nominal Insulation Thick- ness |
Nominal Inner Sheath Thick-ness |
Nominal |
Nominal Armour Wire Diameter |
Nominal Outer Sheath Thick-ness |
|
|
No.x3xmm2 |
mm |
mm |
mm |
mm |
mm |
RE-2X(St)HSWAH 1T0.5 |
1x3x0.50 |
0.35 |
0.8 |
5.4 |
0.9 |
1.3 |
RE-2X(St)HSWAH 1T0.75 |
1x3x0.75 |
0.38 |
0.9 |
6.1 |
0.9 |
1.3 |
RE-2X(St)HSWAH 1T1.0 |
1x3x1.0 |
0.4 |
0.9 |
6.6 |
0.9 |
1.3 |
RE-2X(St)HSWAH 1T1.3 |
1x3x1.3 |
0.45 |
0.9 |
7.2 |
0.9 |
1.3 |
RE-2X(St)HSWAH 1T1.5 |
1x3x1.5 |
0.45 |
0.9 |
7.5 |
0.9 |
1.3 |
Note : Other conductor sizes & core configurations are available upon request.