FIREGUARD Flame Retardant Cables | |||
Fire retardant cable(Fireguard)
300/500V PVC Insulated, Non-sheathed Power Cables (Single Core)
FGD100 05V-U/R/K (CU/PVC 300/500V Class 1/2/5)
BS Code: 2491X
HAR Code: H05V-U, H05V-R, H05V-K
APPLICATION
This cables are mainly used in power stations, mass transit underground passenger systems, airports,
petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS
Basic design to BS EN 50525-2-31(formerly BS 6004:2000)
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2 |
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor |
H05V-U |
Class 1 solid copper conductor to BS EN 60228. |
H05V-R |
Class 2 stranded copper conductor to BS EN 60228. |
|
H05V-K |
Class 5 stranded copper conductor to BS EN 60228. |
|
Insulation |
PVC Type TI 1 according to BS EN 50363-3 |
COLOUR CODE
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bicolours of any
combination of the above mono-colours are permitted.
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation (PVC) |
70°C |
|
Maximum short circuit temperature (5 Seconds) |
160°C |
|
Minimum bending radius |
Up to 8mm²: |
4 x overall diameter |
8mm² to 12mm² |
5 x overall diameter |
|
Above 12mm² |
6 x overall diameter |
CONSTRUCTION PARAMETERS
Conductor |
FGD100 05V-U/R/K |
|||
No. of Cores x Cross Section |
Class of Conductor |
Nominal Insulation Thickness |
Maximum Overall Diameter |
Approx. Weight |
No.xmm² |
|
mm |
mm |
kg/km |
1x0.50 |
1 |
0.6 |
2.3 |
8 |
1x0.75 |
1 |
0.6 |
2.5 |
11 |
1x1.0 |
1 |
0.6 |
2.7 |
14 |
1x0.50 |
2 |
0.6 |
2.4 |
9 |
1x0.75 |
2 |
0.6 |
2.6 |
12 |
1x1.0 |
2 |
0.6 |
2.8 |
14 |
1x0.50 |
5 |
0.6 |
2.5 |
8 |
1x0.75 |
5 |
0.6 |
2.7 |
11 |
1x1.0 |
5 |
0.6 |
2.8 |
13 |
ELECTRICAL PROPERTIES
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A
Conductor cross-sectional area |
PVC insulated types (HD 21) |
|
single-phase a.c. |
three-phase a.c. |
|
mm² |
A |
A |
0.50 |
3 |
3 |
0.75 |
6 |
6 |
1.0 |
10 |
10 |
Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.: |
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B
Conductor cross-sectional area |
d.c. or single-phase a.c. |
Three-phase a.c. |
mm² |
mV/A/m |
mV/A/m |
0.50 |
93 |
80 |
0.75 |
62 |
54 |
1.0 |
46 |
40 |