FIREGUARD Flame Retardant Cables

Flame Retardant Power & Control Cables

300/500V XLPE Insulated, PVC Sheathed Power Cables (2-4 Cores)

FGD200 05RV-R (CU/XLPE/PVC 300/500V Class 2)

FGD200 05RVMV-R (CU/XLPE/PVC/SWA/PVC 300/500V Class 2)

 

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports,

petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS

Basic design adapted to IEC 60502-1; BS 5467

IEC 60502-1; BS 5467

FIRE PERFORMANCE

Flame Retardance

(Single Vertical

Wire Test)**

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE

0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-

1*; DIN VDE 0482-265-2-1*

Reduced Fire

Propagation

(Vertically-mounted

bundled wires

& cable test)**

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-

004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-

4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC

compound and the cable design.

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.

Insulation: Extruded cross-linked XLPE compound.

Inner Sheath (optional): PVC Compound

Armouring (optional): Galvanized Steel Wire

Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent

and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC

60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable

design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation Colour as per BS7671

  With Earth Conductor Without Earth Conductor
2Cores - Brown, Blue
3Cores Yellow/Green, Brown, Blue Brown, Gray, Black
4Cores Yellow/Green, Brown, Gray, Black Brown, Gray, Black, Blue
5Cores Yellow/Green, Brown, Gray, Black, Blue Brown, Gray, Black, Blue, Black
Above 5 Cores Yellow/Green, Black Numbered Black Numbered

Sheath Colour: Black (other colors upon request)

Physical AND THERMAL PROPERTIES

Temperature range during operation: Max.90°C for XLPE

250°C in short-circuit for 5secs max.

Minimum bending radius: 6 x Overall Diameter (unarmoured cable)

10 x Overall Diameter (armoured cable)

CONSTRUCTION PARAMETERS

Conductor FGD200 05RV-R FGD200 05RVMV-R
No. of Core
X
Cross
Section
No./Nominal
Diameter of
Strands
Nominal
Insulation
Thickness
Unarmoured Armoured
Nominal
Overall
Diameter
Approx.
Weight
Diameter
Under
Armour
Armour
Wire
Diameter
Nominal
Overall
Diameter
Approx.
Weight
Noxmm2 No./mm mm mm kg/km mm mm mm kg/km
2x1.5 7/0.53 0.50 6.5 65 6.5 0.9 11.2 246
2x2.5 7/0.67 0.50 7.3 91 7.3 0.9 12.0 292
2x4 7/0.85 0.50 8.4 131 8.4 0.9 13.1 360
3x1.5 7/0.53 0.50 6.9 81 6.9 0.9 11.6 275
3x2.5 7/0.67 0.50 7.8 116 7.8 0.9 12.5 331
3x4 7/0.85 0.50 9.0 169 9.0 0.9 13.7 413
4x1.5 7/0.53 0.50 7.6 101 7.6 0.9 12.3 309
4x2.5 7/0.67 0.50 8.6 144 8.6 0.9 13.3 380
4x4 7/0.85 0.50 9.9 213 9.9 0.9 14.6 479

Electrical Properties

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

FGD200 05RV-R
Current-Carrying Capacities (Amp)

Conductor cross- sectional area Reference Method
4 (enclosed in conduit
in thermally insulating wall etc)
Reference Method 3 (enclosed in conduit on
a wall or in trunking etc)
Reference Method
1 (clipped direct)
Reference Method 11 (on a perforated cable tray, horizontal or vertical) Reference Method 12 (free air)
Horizontal flat spaced Vertical flat spaced Trefoil
  2 cables, single- phase a.c. or d.c. 3 or 4 cables,
3-phase a.c.
2 cables, single- phase a.c. or d.c 3 or 4 cables,
3-phase a.c.
2 cables, single- phase a.c. or d.c. flat and touching 3 or 4 cables,
3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c. or flat and touching 3 or 4 cables,
3-phase a.c. flat and touching or trefoil
2 cables, single- phase a.c. or d.c.
or 3 c ables three phase
2
cables, single- phase a.c. or d.c.
or 3 cables three
phase
3 cables, trefoil
3-phase a.c.
1 2 3 4 5 6 7 8 9 10 11 12
mm2 A A A A A A A A A A A
1.5 18 17 22 19 25 23 - - - - -
2.5 24 23 30 26 34 31 - - - - -
4 33 30 40 35 46 41 - - - - -

Voltage Drop (Per Amp Per Meter)

Nominal
Cross
Section
Area
2 cables
d.c.
2 cables, single-phase a.c. 3 or 4 cables, 3-phase a.c.
Ref. Methods 3
and 4 (enclosed
in conduit etc,
in or on a wall)
Ref. Methods 1
and 11 (clipped
direct or on trays
touching)
Ref. Methods 3
and 4 (enclosed
in conduit etc,
in or on a wall)
Ref. Methods 1,
11 and 12 (in
trefoil)
Ref. Methods 1 and
11(Flat and touching)
1 2 3 4 5 6 7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.5 31 31 27 27 27 27
2.5 19 19 16 16 16 16
4 33 12 10 10 10 10

FGD200 05RVMV-R
Current-Carrying Capacities (Amp)

Conductor
crosssectional
area
Reference Method 1
(clipped
direct)
Reference Method 11 (on
a perforated horizontal
cable tray or Reference
Method 13 [free air] )
In single-way ducts Laid direct in ground
one 2-core
cable single
phase a.c.
or d.c.
one 3-core or
4-core cable
3-phase a.c.
one 2-core
cable single
phase a.c.
or d.c.
one 3-core or
4-core cable
3-phase a.c.
one 2-core
cable single
phase a.c.
or d.c.
one 3-core or
4-core cable
3-phase a.c.
one 2-core
cable single
phase a.c.
or d.c.
one 3-core or
4-core cable
3-phase a.c.
1 2 3 4 5 6 7 8 9
mm2 A A A A A A A A
1.5 27 23 29 25 - 23 - 28
2.5 36 31 39 33 - 30 - 36
4 49 42 52 44 - 40 - 48

Voltage Drop (Per Amp Per Meter)

Nominal
Cross
Section Area
2 cables d.c. 2 cables, single- phase a.c. 3 or 4 cables, 3-phase a.c. 2 cables, single-phase a.c. 3 or 4 cables,
3-phase a.c.
In ducts or in ground In ducts or in ground
1 2 3 4 5 6
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.5 31 31 27 31 25
2.5 19 19 16 19 15
4 12 12 10 12 9.7