Instrumentation Cables | ||||||||||||||
|
Instrumentation Cables
Product Name/Code: 16-2-6C SCREENED
Application:Multi-conductor-audio,control.& Instrumentation Cables
Electrical Performance:
Max.Conductor DC Resistance at 20 ℃(Ω/Km) 22.49 < 37.04
Operating Temperature( ℃ ) 74 80
Voltage Rating(V) 1499 30
20 ℃ Insulation Resistance(M Ω .KM) > 200
Fire Performance :
Flame Propagation Test to IEC 60332 Part 1 and Part 3
Determination of the amount Halogen Acid Gas to IEC 60754 Part 1
Smoke Density Test to IEC 61034
Oxygen Index Test to BS 2863 or ISO 4589-2
Temperatre Index Test to BS 2782 or ISO 4589-3
Fire Resistant Test to IEC 60331-24
Construction | |
6 Core | Stranded Tinned Copper |
AWG | 18 |
Construction | T0.20 x 16 |
Conductor Diameter(mm) | 0.92 |
Insulation | PVC |
Thickness | 0.44 |
Insulation Dia.(mm) | 1.80 |
Mylar Spiral (over lapping,%) | >=25% |
Screening | Tinned Copper |
Construction(mm) | T0.12 x 16 x 8 |
Coverage Area(%) | > 70% |
Nylon rip cord | 210D |
Sheathing | PVC OR LSF |
Thickness(mm) | 1.8 |
Diameter(mm) | 8.70 |
Sheathing Compound | PVC/LSF/LSOH |
Core Identification/Color Code | According to customer request |
Bending Radius | 6xOverall Diameter |
Temperature Rating | 70C |
Voltage Rating | 300/500V |