BS 6622 Single Core Unarmoured (Copper Wire Screened) 11kV XLPE Stranded Aluminium Conductors
Construction
cross-sectional area mmsq | Minimum average thickness of insulation mm | Nominal diameter over insulation mm |
Nominal area of copper wire screen mm sq |
Nominal average thickness of PVC oversheath mm |
Nominal overall diameter of cable mm |
70 | 3.4 | 18.8 | 16 | 1.7 | 25.7 |
95 | 3.4 | 20.5 | 16 | 1.8 | 27.4 |
120 | 3.4 | 22.0 | 16 | 1.8 | 29.2 |
150 | 3.4 | 23.3 | 16 | 1.9 | 30.5 |
185 | 3.4 | 25.1 | 16 | 1.9 | 32.5 |
240 | 3.4 | 27.3 | 25 | 2 | 34.9 |
300 | 3.4 | 29.6 | 25 | 2.1 | 37.2 |
400 | 3.4 | 32.3 | 35 | 2.2 | 40.1 |
500 | 3.4 | 35.2 | 35 | 2.3 | 13.2 |
630 | 3.4 | 39.1 | 35 | 2.4 | 17.4 |
Installation
cross-sectional area mmsq | Approximate cable weight kg/m | Nominal drum length m |
Minimum bending radius mm | Nominal internal diameter of ducts mm |
70 | 0.8 | 1000 | 400 | 100 |
95 | 0.9 | 1000 | 450 | 100 |
120 | 1.1 | 500 | 450 | 100 |
150 | 1.2 | 500 | 450 | 100 |
185 | 1.3 | 500 | 500 | 100 |
240 | 1.7 | 500 | 550 | 100 |
300 | 1.9 | 500 | 600 | 100 |
400 | 2.3 | 500 | 650 | 100 |
500 | 2.7 | 500 | 650 | 100 |
630 | 3.2 | 400 | 750 | 100 |
Electrical Performance
cross-sectional area mmsq | Maximum DC resistance of conductor at 20 ℃ uohms/m | Maximum AC resistance of conductor at 90 ℃ uohms/m | Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m |
70 | 443 | 568 | 121 | 581 | 288 | 0.58 |
95 | 320 | 410 | 114 | 426 | 323 | 0.65 |
120 | 253 | 325 | 110 | 343 | 353 | 0.71 |
150 | 206 | 265 | 107 | 286 | 380 | 0.76 |
185 | 164 | 211 | 104 | 234 | 416 | 0.83 |
240 | 125 | 161 | 100 | 190 | 460 | 0.92 |
300 | 100 | 130 | 96.9 | 162 | 506 | 1.01 |
400 | 77.8 | 102 | 94.0 | 138 | 561 | 1.12 |
500 | 60.5 | 81 | 91.3 | 122 | 619 | 1.24 |
630 | 46.9 | 64 | 88.1 | 109 | 697 | 1.37 |
Ratings
Cross-sectional area mmsq |
Current Ratings | Short circuit ratings | |||
Laid direct in ground Amps |
Drawn into ducts Amps |
Laid in air Amps |
One second short circuit rating of conductor KA |
One second short circuit rating of copper per core KA |
|
70 | 210 | 215 | 240 | 6.3 | 2.6 |
95 | 250 | 255 | 295 | 8.5 | 2.6 |
120 | 280 | 285 | 335 | 11.0 | 2.6 |
150 | 320 | 315 | 380 | 13.5 | 2.6 |
185 | 360 | 350 | 435 | 17.0 | 2.6 |
240 | 415 | 405 | 510 | 22.3 | 4.3 |
300 | 475 | 455 | 600 | 28.0 | 4.3 |
400 | 540 | 510 | 700 | 36.6 | 5.8 |
500 | 610 | 570 | 810 | 46.2 | 5.8 |
630 | 680 | 640 | 930 | 58.3 | 5.8 |