Power Cables | ||||||||||||
|
BS 6622 Single Core Armoured 15KV XLPE Stranded Copper Conductors
Construction
cross-sectional area mm2 | Minimum average thickness of insulation mm | Nominal area of copper tape screen mm2 |
Nominal thickness of PVC bedding mm |
Nominal number and diameter of armoured wires no./mm | Nominal thickness of PVC oversheath mm |
Nominal overall diameter of cable mm |
50 | 4.5 | 19.4 | 1.2 | 43/1.6 | 1.9 | 30.3 |
70 | 4.5 | 21.2 | 1.2 | 46/1.6 | 1.9 | 32.1 |
95 | 4.5 | 22.9 | 1.2 | 40/2.0 | 2.0 | 34.8 |
120 | 4.5 | 24.4 | 1.2 | 42/2.0 | 2.1 | 36.5 |
150 | 4.5 | 25.7 | 1.2 | 44/2.0 | 2.1 | 37.8 |
185 | 4.5 | 27.5 | 1.2 | 46/2.0 | 2.2 | 40.0 |
240 | 4.5 | 29.7 | 1.2 | 49/2.0 | 2.3 | 42.4 |
300 | 4.5 | 32.0 | 1.2 | 53/2.0 | 2.3 | 44.7 |
400 | 4.5 | 34.7 | 1.3 | 46/2.5 | 2.5 | 49.0 |
500 | 4.5 | 37.6 | 1.3 | 49/2.5 | 2.6 | 52.1 |
630 | 4.5 | 41.0 | 1.4 | 53/2.5 | 2.7 | 55.9 |
800 | Please refer to our technical department for further information | |||||
1000 |
Installation
cross-sectional area mm2 | Approximate cable weight kg/m | Nominal drum length m |
Minimum bending radius mm | Nominal internal diameter of ducts mm |
50 | 1.4 | 1000 | 550 | 100 |
70 | 1.7 | 1000 | 600 | 100 |
95 | 2.1 | 500 | 650 | 100 |
120 | 2.4 | 500 | 700 | 100 |
150 | 2.7 | 500 | 700 | 100 |
185 | 3.2 | 500 | 750 | 100 |
240 | 3.8 | 500 | 800 | 100 |
300 | 4.5 | 500 | 850 | 100 |
400 | 5.6 | 300 | 900 | 100 |
500 | 6.7 | 300 | 950 | 100 |
630 | 8.2 | 300 | 1050 | 100 |
800 | Please refer to our technical department for further information | |||
1000 |
Electrical Performance
cross-sectional area mm2 | Maximum DC resistance of conductor at 20 ℃ uohms/m | Maximum AC resistance of conductor at 90 ℃ uohms/m | Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m |
50 | 387 | 494 | 144 | 514 | 204 | 0.56 |
70 | 268 | 343 | 135 | 368 | 232 | 0.63 |
95 | 193 | 248 | 129 | 279 | 258 | 0.7 |
120 | 153 | 196 | 124 | 232 | 281 | 0.77 |
150 | 124 | 159 | 121 | 198 | 301 | 0.82 |
185 | 99.1 | 128 | 117 | 172 | 329 | 0.9 |
240 | 75.4 | 98 | 113 | 148 | 363 | 0.99 |
300 | 60.1 | 80 | 108 | 133 | 398 | 1.09 |
400 | 47 | 64 | 107 | 124 | 439 | 1.2 |
500 | 36.6 | 51 | 103 | 114 | 483 | 1.32 |
630 | 28.3 | 42 | 99.5 | 107 | 534 | 1.46 |
800 | Please refer to our technical department for further information | |||||
1000 |
Ratings
Cross-sectional area mm2 |
Current Ratings | Short circuit ratings | |||
Laid direct in ground Amps |
Drawn into ducts Amps |
650Laid in air Amps |
One second short circuit rating of conductor KA |
One second short circuit rating of copper per core KA |
|
50 | 220 | 220 | 250 | 6.8 | Typically less then 1kA |
70 | 270 | 260 | 310 | 9.8 | |
95 | 320 | 305 | 375 | 13.3 | |
120 | 360 | 640 | 430 | 17.2 | |
150 | 410 | 375 | 490 | 21.2 | |
185 | 455 | 410 | 550 | 26.6 | |
240 | 520 | 460 | 650 | 34.9 | |
300 | 580 | 500 | 740 | 43.8 | |
400 | 650 | 530 | 840 | 57.3 | |
500 | 710 | 570 | 930 | 72.3 | |
630 | 760 | 620 | 1040 | 91.2 | |
800 | Please refer to our technical department for further information | ||||
1000 |