Power Cables
PVC Insulated & Sheathed Unarmoured XLPE Insulated PVC/LSOH Sheathed LSOH Insulated Conduit Wires Fire Resistant Medium Voltage

Power Cables

2-5kV XLPE Insulated PVC Sheathed Unarmoured Power Cable 100/133% Levels

100/133% Insulation Levels (single conductor)

Conductor Insulation
thickness
( mm )
Sheath
thickness
( mm )
Overall Dia.
approx.
( mm )
AC Test
voltage
( kV / 5 min )
Cable weight
approx.
( kg / km )
Size
(AWG or MCM)
Construction
( No. / mm )
Outside Dia.
( mm )
8
6
4
2
1
7/1.23
7/1.56
7/1.96
7/2.47
19/1.69
3.70
4.67
5.88
7.42
8.43
2.29
2.29
2.29
2.29
2.29
1.14
1.52
1.52
1.52
1.52
12.8
14.6
15.8
17.3
18.4
13
13
13
13
13
246
340
435
580
685
1/0
2/0
3/0
4/0
250
C.C.
C.C.
C.C.
C.C.
C.C.
8.53
9.55
10.74
12.07
13.21
2.29
2.29
2.29
2.29
2.29
1.52
1.52
2.03
2.03
2.03
18.5
19.5
21.8
23.1
24.3
13
13
13
13
13
785
933
1175
1408
1615
300
350
400
500
100
C.C.
C.C.
C.C.
C.C.
C.C.
14.48
15.65
16.74
18.69
20.65
2.29
2.29
2.29
2.29
2.29
2.03
2.03
2.03
2.03
2.03
25.5
26.7
27.8
29.7
31.7
13
13
13
13
13
1872
2126
2388
2888
3424
750
1000
C.C.
C.C.
23.06
26.92
2.29
2.29
2.03
2.03
34.1
38.0
13
13
4178
5433
100/133% Insulation Levels (Three conductor)
Conductor Insulation
thickness
( mm )
Sheath
thickness
( mm )
Overall Dia.
approx.
( mm )
AC Test
voltage
( kV / 5 min )
Cable weight
approx.
( kg / km )
Size
(AWG or MCM)
Construction
( No. / mm )
Outside Dia.
( mm )
8
6
4
2
1
7/1.23
7/1.56
7/1.96
7/2.47
19/1.69
3.70
4.67
5.88
7.42
8.43
2.29
2.29
2.29
2.29
2.29
2.03
2.03
2.03
2.03
2.03
26.4
28.5
31.1
34.4
36.7
13
13
13
13
13
864
1080
1382
1847
2176
1/0
2/0
3/0
4/0
250
C.C.
C.C.
C.C.
C.C.
C.C.
8.53
9.55
10.74
12.07
13.21
2.29
2.29
2.29
2.29
2.29
2.03
2.03
2.03
2.79
2.79
36.8
39.0
41.6
46.2
48.6
13
13
13
13
13
2480
2955
3542
4447
5101
300
350
400
C.C.
C.C.
C.C.
14.48
15.65
16.74
2.29
2.29
2.03
2.79
2.79
2.79
51.3
53.9
56.3
13
13
13
5907
6725
7545
* C.C.: Stranded and compacted circular.