BS 6622 Three Core Armoured 6.6kV XLPE Stranded Copper Conductors
Construction
cross-sectional area mmsq | Minimum average thickness of insulation mm | Nominal area of copper tape screen mmsq | Nominal thickness of PVC bedding | Nominal number and diameter of armoured wires no./ mm | Nominal thickness of PVC oversheath mm | Nominal overall diameter of cable mm |
50 | 2.5 | 15.0 | 1.3 | 45/2.5 | 2.5 | 48.4 |
70 | 2.5 | 16.8 | 1.3 | 49/2.5 | 2.6 | 52.4 |
95 | 2.5 | 18.5 | 1.4 | 54/2.5 | 2.7 | 56.5 |
120 | 2.5 | 20.0 | 1.5 | 57/2.5 | 2.8 | 60.1 |
150 | 2.5 | 21.3 | 1.5 | 60/2.5 | 2.9 | 63.1 |
185 | 2.5 | 23.1 | 1.6 | 65/2.5 | 3 | 67.4 |
240 | 2.6 | 25.5 | 1.7 | 71/2.5 | 3.2 | 73.2 |
300 | 2.8 | 28.3 | 1.8 | 62/3.15 | 3.5 | 81.3 |
400 | 3.0 | 31.4 | 2.0 | 69/3.15 | 3.7 | 88.8 |
Installation
cross-sectional area mmsq | Approximate cable weight kg/m | Nominal drum length m |
Minimum bending radius mm | Nominal internal diameter of ducts mm |
50 | 4.9 | 750 | 600 | 100 |
70 | 5.8 | 750 | 650 | 100 |
95 | 6.9 | 500 | 700 | 100 |
120 | 7.9 | 500 | 750 | 100 |
150 | 8.9 | 500 | 800 | 125 |
185 | 10.4 | 450 | 850 | 125 |
240 | 12.7 | 400 | 900 | 125 |
300 | 16.0 | 400 | 1000 | 125 |
400 | 19.4 | 350 | 1100 | - |
Electrical Performance
cross-sectional area mmsq | Maximum DC resistance of conductor at 20 ℃ uohms/m | Maximum AC resistance of conductor at 90 ℃ uohms/m | Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m |
50 | 387 | 494 | 108 | 506 | 332 | 0.40 |
70 | 268 | 343 | 102 | 358 | 383 | 0.46 |
95 | 193 | 248 | 96.2 | 266 | 432 | 0.52 |
120 | 153 | 196 | 93.1 | 217 | 474 | 0.57 |
150 | 124 | 159 | 90.8 | 183 | 511 | 0.61 |
185 | 99.1 | 128 | 88.1 | 155 | 562 | 0.67 |
240 | 75.4 | 98 | 85.9 | 130 | 602 | 0.72 |
300 | 60.1 | 80 | 84.7 | 117 | 622 | 0.75 |
400 | 47.0 | 64 | 83.2 | 105 | 648 | 0.78 |
Ratings
Cross-sectional area mmsq |
Current Ratings | Short circuit ratings | |||
Laid direct in ground Amps |
Drawn into ducts Amps |
Laid in air Amps |
One second short circuit rating of conductor KA |
One second short circuit rating of copper per core KA |
|
50 | 210 | 180 | 220 | 6.8 | Typically Less Than 1kA |
70 | 255 | 215 | 270 | 9.8 | |
95 | 300 | 255 | 330 | 13.3 | |
120 | 340 | 290 | 375 | 17.2 | |
150 | 380 | 330 | 430 | 21.2 | |
185 | 430 | 370 | 490 | 26.6 | |
240 | 490 | 425 | 570 | 34.9 | |
300 | 540 | 470 | 650 | 43.8 | |
400 | 590 | 520 | 700 | 57.3 |