Power Cables | ||||||||||||
|
Power Cables
3800/6600VFour Core, XLPE Insulated, PVC Sheathed, Armoured to BS 6622
Voltage Rating :3800/6600V
Construction
Conductor : Plain annealed stranded copper conductor
Insulation : XLPE Compound
Copper tape Screen:Copper tape Screen
Filler (where applicable) :Polypropylene yarn
Inner Jacket:PVC jacket
Armouring (for armoured cable) :Aluminium wire (single core) or Galvanized steel wires (multicore)
Separator Tape:Galvanized Steel Tape
Sheath :PVC/LSOH compound
Colour of identification : Natural
Sheath Colour : Black, Grey or White
Conductor Nominal Cross-sectional Area(mm2) | Insulation Thickness (mm) | Nominal Diameter over insulation(mm) | Nominal area of copper tape screen per core(mm2) | Nominal Thickness of PVC inner jacket(mm) | Nominal number and diameter of armour wires (No./mm) | Nominal thickness of PVC oversheath(mm) | Nominal overall diameter (mm) |
Approx. cable weight kg/km |
25 | 2.5 | 13.1 | 3.5 | 1.3 | 49/2.0 | 2.5 | 43.9 | 3860 |
35 | 2.5 | 14.2 | 3.6 | 1.4 | 52/2.0 | 2.5 | 46.2 | 4637 |
50 | 2.6 | 15.5 | 4 | 1.5 | 46/2.5 | 2.8 | 50.8 | 5250 |
70 | 2.6 | 17 | 4.3 | 1.5 | 49/2.5 | 2.8 | 55 | 6352 |
95 | 2.6 | 18.9 | 4.8 | 1.6 | 54/2.5 | 3 | 59.5 | 7790 |
120 | 2.6 | 20.2 | 5.1 | 1.6 | 57/2.5 | 3 | 64 | 9120 |
150 | 2.7 | 21.8 | 5.5 | 1.7 | 60/2.5 | 3.2 | 66.9 | 10528 |
185 | 2.7 | 23.8 | 5.8 | 1.7 | 65/2.5 | 3.2 | 70.5 | 12371 |
240 | 2.7 | 26 | 6.5 | 1.8 | 71/2.5 | 3.5 | 76.6 | 14910 |
300 | 2.8 | 28.9 | 7.2 | 2 | 62/3.15 | 3.7 | 84.6 | 17348 |
400 | 3 | 32 | 8 | 2 | 69/3.15 | 3.9 | 92 | 21050 |