Windmill Cables
EPR/HFXLEVA LSOH 0.6/1kV Torsion Resistant Power Cable HFEPR/HFEVA 0.6/1kV LSOH Screened Torsion Resistant Power Cable Al Conductor EPR/XLEVA 0.6/1kV LSOH Power Cable 90℃ more

  Windmill Cables

H05V-K/H07V-K Internal Wiring Cable

 

Application

These cables are designed for the intenal wiring of devices, distributor and switchboards and also for protective

laying to the lightings, suitable for laying in tubes, under and surface mounting of plasters and also in closed

installation conduits.

Standards

DIN VDE 0281 part 3

HD 21.3 S3

IEC 60227-3

Construction

Windmill Cables

Conductor: Stranded bare copper, class 5 according to DIN VDE 0295/HD 383/ IEC 60228.

Insulation: PVC.

Technical Data

Rated Voltage U0/U (Um) 300/500V(H05V-K); 450/750V(H07V-K)
Operating Temperatures flexing: -5℃~+70℃; fixed: -30℃~+80℃
Minimum Bending Radius 15×OD
Flame Retardant VDE 0482-332-1-2/IEC 60332-1
Silicone Free Yes

Dimensions and Weight

H05V-K

Construction Nominal Overall Diameter Nominal Weight
No. of cores×mm² mm kg/km
1×0.5 2.1 9
1×0.75 2.4 12
1×1 2.6 15

H07V-K

Construction Nominal Overall Diameter Nominal Weight
No. of cores×mm² mm kg/km
1×1.5 3.0 24
1×2.5 3.7 35
1×4 4.3 51
1×6 4.9 71
1×10 6.5 118
1×16 8.0 180
1×25 9.8 278
1×35 11.0 375
1×50 13.0 560
1×70 15.5 780
1×95 17.0 952
1×120 19.7 1200
1×150 21.3 1505
1×185 23.5 1845
1×240 27.4 2400