Airport Cable | |||
FAA L-824 Type B Shielded 5kV
Applications
Airport cables are used for interconnecting the transformers and the current regulator of airfield lighting systems
in series circuits, suitable for fixed applications such as taxiways, runways, navigational aids, and obstruction
lighting, can be installed in conduit and direct burial.
Standards
FAA L-824 Type B
ICEA S-93-639 / NEMA WC74
Construction
Conductor: Stranded tinned copper conductor.
Insulation: EPR.
Semi-Conductor: Helically applied semi-conducting tape.
Shield: Tinned copper tape.
Separator: Separation tape.
Sheath: CPE.
Technical Data
Rated Voltage Uo/U (Um) :5kV
Maximum Conductor Temperature :90℃
Short Circuit Temperature :250℃
Operating Temperatures :-40℃~+85℃
Minimum Bending Radius :12×OD
Halogen Free :Yes
Abrasion Resistant :Yes
UV Resistant :Yes
Oil Resistant :Yes
Dimensions and Weight
Construction | No. of Strand | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Nominal Weight | ||||
---|---|---|---|---|---|---|---|---|---|
No. ×mm²/ AWG |
- | mm | inches | mm | inches | mm | inches | kg/km | lbs/kft |
1×6mm² | 7 | 2.3 | 0.09 | 1.2 | 0.05 | 11.1 | 0.44 | 194 | 130 |
1×8 | 7 | 2.3 | 0.09 | 1.2 | 0.05 | 11.7 | 0.46 | 225 | 151 |