Halogen-free, +145°C wind-power installations Cable
Application
This special cable is designed for generator connection in wind-power installations.
Construction
Tinned copper, fine wire conductors to DIN VDE 0295 cl. 5 and IEC 60228 cl. 5;
Special-insulation, polyolefin-copolymer halogen-free, flame retardant;
Jacket color black.
Properties:
Halogen-free, no liberation of toxic or corrosive vapors
Lower propagation of fire
Low development of smoke
Good abrasion resistant
Good resistance to oil and weather
Resistant to UV-radiation and ozone
Thermal class B
The materials used in manufacture are cadmium free and contain no silicone and are free of substances harmful
to the wetting properties of lacquers
Temperature range:
flexing -20°C to +120°C, fixed installation -55°C to +145°C
Nominal voltage:
U0/U 0,6/1 kV
test voltage:
3500 V
Minimum bending radius:
for flexing application,12,5-15x cable Ø
Conductors x cross-sec. mm² |
Outer Diameter |
Copper weight kg/km |
Weight ca. kg/km |
AWG |
1x6 | 5.4 | 58.0 | 70.0 | 10 |
1x10 | 6.8 | 96.0 | 119.0 | 8 |
1x16 | 8.5 | 154.0 | 180.0 | 6 |
1x25 | 10.3 | 240.0 | 270.0 | 4 |
1x35 | 11.8 | 336.0 | 373.0 | 2 |
1x50 | 13.9 | 480.0 | 528.0 | 1 |
1x70 | 16.0 | 672.0 | 728.0 | 2/0 |
1x95 | 18.5 | 912.0 | 966.0 | 3/0 |
1x120 | 20.5 | 1152.0 | 1230.0 | 4/0 |
1x150 | 22.1 | 1440.0 | 1530.0 | 300 kcmil |
1x185 | 24.8 | 1776.0 | 1880.0 | 350 kcmil |
1x240 | 27.7 | 2304.0 | 2500.0 | 500 kcmil |