Special Cables
Trailing cables Cables for renewable energy Single Conductor Airport 400Hz Truck cables more

Shielded, High flexible PVC single conductor

Application

Applications as described above, additionally optimal compliance with electromagnetic compatibility (EMC)

requirements on account of the approx. 85% coverage by the braided shielding.

Cable Construction

Bare copper, extra fine wire conductor to DIN VDE 0295 cl. 6 and IEC 60228 cl. 6;

PVC insulation, green-yellow;

PVC jacket compound TM2;

Jacket color gray;

Tinned copper braid, coverage approx. 85% .

Temperature range:

flexing -5°C to +80°C; fixed installation -40°C to +80°C

Nominal voltage:

U0/U 600/1000 V

A.C. test voltage, 50 Hz:

3000 V

Minimum bending radius:

for flexible installation; approx. 5x cable Ø

Properties

PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/ EN 50265-2-1/ IEC 60332-1

(equivalent DIN VDE 0472 part 804 test method B)

Chemical resistance see table Technical Information

Shielded, High flexible PVC single conductor

Conductors x cross-sec. mm² Outer
Diameter
Copper weight
kg/km
Weight
ca. kg/km
AWG
1x2.5 5.9 34.0 55.0 14
1x4 6.5 50.0 75.0 12
1x6 8.3 88.0 125.0 10
1x10 8.7 124.0 170.0 8
1x16 10.3 190.0 300.0 6
1x25 12.4 260.0 420.0 4
1x35 13.7 405.0 620.0 2
1x50 15.4 560.0 825.0 1
1x70 17.5 780.0 1090.0 2/0
1x95 21.0 1030.0 1395.0 3/0
1x120 22.4 1285.0 1770.0 4/0
1x150 24.3 1430.0 1930.0 300 kcmil
1x185 26.5 1940.0 2635.0 350 kcmil
1x240 30.3 2530.0 3380.0 500 kcmil
1x300 35.0 2950.0 3500.0 600 kcmil