Aerial Bundled Cables 
   

Aerial Bundled Cables

Aluminium Conductor Cables

MV Aerial Bundled Conductor (ABC) Cables

Application

Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential

premises.

Standard

Basic design to IEC 60502 / AS/NZS 3599-1 standards

Construction

aluminium conductor cables

1x75Ohm RG59 Coaxial Cable

Phase Conductor: Circular compacted stranded H68 aluminium to BS2627.

Conductor Screen: Extruded semi-conductive layer.

insulation: XLPE.

insulation Screen: Extruded semi-conductive layer.

metallic Screen(optional): Copper wire screen or copper tape screen.

Separator: Semi-conductive swellable tape.

outer Sheath: HDPE.

Support Conductor: Galvanized steel wires.

Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand

lay.

Construction Parameters

IEC 60502 6.35/11 kV ABC for overhead distribution lines

 

Number of Cores xNominal
Cross Section

Phase Conductor

Messenger Suspension Unit

Continuous current rating
at 300C
ambient temp

 

Stranding

Nominal Sectional Area

Maximum Conductor Resistance

 

Stranding

Nominal Sectional Area

 

Breaking Load

No.×mm²

No.×mm

mm²

Ω/Km

No.×mm

mm²

KN

A

3X50 + 1X25

19/1.78

50

0.641

7/3.0

25

60

116

3X70 + 1X50

19/2.14

70

0.443

7/3.15

50

62

210

3X95+ 1X50

19/2.52

95

0.32

7/3.0

50

60

173

3X185+1X120

37/2.52

185

0.164

7/4.67

120

150

259

3X150 +1X50

37/2.25

150

0.206

7/3.15

50

62

365

3X240 +1X50

61/2.25

240

0.125

7/3.15

50

62

500

Other cross-sections can be offered upon request.

iEC 60502 19/33 kV ABC for overhead distribution lines

 

Number of Cores xNominal
Cross Section

Phase Conductor

Messenger Suspension Unit

Continuous current rating
at 300C
ambient temp

 

Stranding

Nominal Sectional Area

Maximum Conductor Resistance

 

Stranding

Nominal Sectional Area

 

Breaking Load

No.×mm²

No.×mm

mm²

Ω/Km

No.×mm

mm²

KN

A

3X50 + 1X25

19/1.78

50

0.641

7/3.0

25

60

165

3X150+ 1X50

37/2.25

150

0.206

7/3.0

50

60

315

3X185+1X70

37/2.52

185

0.164

7/3.57

70

91

355

3X70 +1X50

19/2.14

70

0.443

7/3.15

50

62

250

3X150 +1X50

37/2.25

150

0.206

7/3.15

50

62

370

Other cross-sections can be offered upon request.


AS/nZS 3599 Part 1 6.35/11 kV Al/XlPE /HdPE non-screened Cables

 

Number of Cores xNominal
Cross Section

Phase Conductor

Messenger Suspension
Unit

 

Nominal Sectional Area

 

Breaking Load

Diameter of    Conductor

Thickness of    Insulation

Thickness of    Insulation Screen

Thickness of
Sheath

 

Stranding

No.×mm²

mm

mm

mm

mm

No.×mm

mm²

KN

3x35

6.9

3.4

0.8

1.2

7/4.75

52.4

1370

3x50

8.1

3.4

0.8

1.2

7/4.75

54.6

1530

3x70

9.7

3.4

0.8

1.2

7/4.75

57.8

1790

3x95

11.4

3.4

0.8

1.2

7/4.75

61.3

2100

3x120

12.8

3.4

0.8

1.2

19/3.50

67.3

2540

3x150

14.2

3.4

0.8

1.2

19/3.50

70.1

2840

3x185

15.7

3.4

0.8

1.2

19/3.50

73.1

3190

Other cross-sections can be offered upon request.

AS/nZS 3599 Part 1 6.35/11 kV Al/XlPE /CWS/HdPE Screened Cables

Number of Cores xNominal Cross Section

 

Diameter of    Conductor

 

Thickness of    Insulation

Thickness of    Insulation Screen

 

Copper Wire Screen Stranding

 

Thickness of
Sheath

 

Galvanized Steel Wire Stranding

 

Nominal Sectional Area

 

Breaking Load

No.×mm²

mm

mm

mm

No.×mm

mm

No.×mm

mm²

KN

light duty Screen

3x35

6.9

3.4

0.8

25/0.85

1.8

7/2.00

54.1

1820

3x35

6.9

3.4

0.8

25/0.85

1.8

19/2.00

58.1

2130

3x50

8.1

3.4

0.8

25/0.85

1.8

19/2.00

60.4

2300

3x70

9.7

3.4

0.8

25/0.85

1.8

19/2.00

63.6

2570

3x95

11.4

3.4

0.8

25/0.85

1.8

19/2.00

67.0

2900

3x120

12.8

3.4

0.8

25/0.85

1.8

19/2.00

69.8

3190

3x150

14.2

3.4

0.8

25/0.85

1.9

19/2.00

73.0

3530

3x185

15.7

3.4

0.8

25/0.85

1.9

19/2.00

76.0

3890

 

Number of Cores xNominal Cross Section

 

Diameter of    Conductor

 

Thickness of    Insulation

Thickness of    Insulation Screen

 

Copper Wire Screen Stranding

 

Thickness of
Sheath

 

Galvanized Steel Wire Stranding

 

Nominal Sectional Area

 

Breaking Load

No.×mm²

mm

mm

mm

No.×mm

mm

No.×mm

mm²

KN

Heavy duty Screen

3x35

6.9

3.4

0.8

40/0.85

1.8

7/2.00

54.1

2050

3x35

6.9

3.4

0.8

40/0.85

1.8

19/2.00

58.1

2360

3x50

8.1

3.4

0.8

23/1.35

1.8

19/2.00

62.4

2820

3x70

9.7

3.4

0.8

32/1.35

1.8

19/2.00

65.6

3440

3x95

11.4

3.4

0.8

39/1.35

1.8

19/2.00

69.0

4030

3x120

12.8

3.4

0.8

39/1.35

1.8

19/2.00

71.8

4320

3x150

14.2

3.4

0.8

39/1.35

1.9

19/2.00

75.0

4670

3x185

15.7

3.4

0.8

39/1.35

1.9

19/2.00

78.0

5020

Other cross-sections can be offered upon request.

AS/nZS 3599 Part 1 12.7/22 kV Al/XlPE /HdPE non-screened Cables

 

Number of Cores xNominal
Cross Section

Phase Conductor

Messenger Suspension
Unit

 

Nominal Sectional Area

 

Breaking Load

Diameter of    Conductor

Thickness of    Insulation

Thickness of    Insulation Screen

Thickness of
Sheath

 

Stranding

No.×mm²

mm

mm

mm

mm

No.×mm

mm²

KN

3x35

6.9

5.5

0.8

1.2

7/4.75

61.0

1780

3x50

8.1

5.5

0.8

1.2

7/4.75

63.3

1970

3x70

9.7

5.5

0.8

1.2

7/4.75

66.5

2260

3x95

11.4

5.5

0.8

1.2

7/4.75

69.9

2600

3x120

12.8

5.5

0.8

1.2

19/3.50

75.9

3070

3x150

14.2

5.5

0.8

1.2

19/3.50

78.7

3390

3x185

15.7

5.5

0.8

1.2

19/3.50

81.7

3760

Other cross-sections can be offered upon request.AS/nZS 3599 Part 1 12.7/22 kV Al/XlPE /CWS/HdPE Screened Cables

 

Number of Cores xNominal Cross Section

 

Diameter of    Conductor

 

Thickness of    Insulation

Thickness of    Insulation Screen

 

Copper Wire Screen Stranding

 

Thickness of
Sheath

 

Galvanized Steel Wire Stranding

 

Nominal Sectional Area

 

Breaking Load

No.×mm²

mm

mm

mm

No.×mm

mm

No.×mm

mm²

KN

light duty Screen

3x35

6.9

5.5

0.8

25/0.85

1.8

7/2.00

62.7

2280

3x35

6.9

5.5

0.8

25/0.85

1.8

19/2.00

66.7

2580

3x50

8.1

5.5

0.8

25/0.85

1.8

19/2.00

69.0

2780

3x70

9.7

5.5

0.8

25/0.85

1.9

19/2.00

72.6

3110

3x95

11.4

5.5

0.8

25/0.85

1.9

19/2.00

76.0

3460

3x120

12.8

5.5

0.8

25/0.85

2.0

19/2.00

79.2

3810

3x150

14.2

5.5

1.0

25/0.85

2.0

19/2.00

82.8

4230

3x185

15.7

5.5

1.0

25/0.85

2.1

19/2.00

86.2

4650

Heavy duty Screen

3x35

6.9

5.5

0.8

40/0.85

1.8

7/2.00

62.7

2510

3x35

6.9

5.5

0.8

40/0.85

1.8

19/2.00

66.7

2810

3x50

8.1

5.5

0.8

23/1.35

1.8

19/2.00

71.0

3300

3x70

9.7

5.5

0.8

32/1.35

1.9

19/2.00

74.6

3970

3x95

11.4

5.5

0.8

39/1.35

1.9

19/2.00

78.0

4600

3x120

12.8

5.5

0.8

39/1.35

2.0

19/2.00

81.2

4950

3x150

14.2

5.5

1.0

39/1.35

2.0

19/2.00

84.8

5360

3x185

15.7

5.5

1.0

39/1.35

2.1

19/2.00

88.2

5790

Other cross-sections can be offered upon request.

Technical Data

Nominal Cross Section Continuous Current Rating
Still air 1m/s wind 2m/s wind
mm² A A A
35 105 145 165
50 125 170 200
70 150 215 250
95 180 260 300
120 205 300 350
150 230 340 395
185 265 390 450