Aerial Bundled Cables 
   

Aerial Bundled Cables

Aluminium Conductor Cables

All Aluminum Alloy Conductor (AAAC) Cables

Application

AAAC is mainly used as bare overhead transmission cable and as primary and secondary distribution cable. It is

also suitable for laying across basins, rivers and valleys where special geographical teatures exist.

Standard

Basic design to BS 3242 / BS EN 50182 / IEC 61089 / ASTM B 399/B 399M / DIN 48201 -6 standards

Construction

Aluminium Conductor Cables

AAAC cable bvconsists of aluminum alloy wires. The aluminum alloy wires are concentrically stranded.

This section deals with heat-treatable magnesium silicon type aluminium alloys to the applicable International

Standard, the electrical and mechanical properties of which all fall within the values suggested by relevant

standard.

Conductors to all other recognized specifications can also be supplied. The alloys referred to have higher

strength but lower conductivity than pure aluminium. Being lighter, alloy conductors can sometimes be used to

advantage in place of the more conventional ACSR; Having lower breaking loads than the later, their use

becomes particularly favourable when ice and wind loadings are low.

Electrical Properties

Density@20ºC 2.70 kg/dm
Temperature Coefficient@20°C 0.00360 (°C)
Resistivity@20°C 0.0326 Ohms mm²/m
Linear Expansivity 23 x10-6(°C)

Service Conditions

Ambient Temperature -5°C - 50°C
Wind Pressure 80 – 130kg/m²
Seismic Acceleration 0.12 - 0.05g
Isokeraunic Level 10 – 18
Relative Humidity 5 – 100%

Construction Parameters

BS 3242

 

Code

AL Nominal Area

Cu Nominal Area Equivalent

 

Total Area

 

Stranding

Overall Diameter

 

Weight

 

mm2

mm2

mm2

No.×mm

mm

kg/km

-

-

6.45

11.7

7/1.47

4.41

32.2

Box

-

9.68

18.8

7/1.85

5.55

51.7

Acacia

-

12.9

21.9

7/2.08

6.24

66.1

Almond

25

16.1

30.1

7/2.34

7.02

82.9

Ceda

30

19.4

35.5

7/2.54

7.62

97.8

-

40

22.6

42.2

7/2.77

8.31

116.4

Fir

50

25.8

47.8

7/2.95

8.85

131.8

Hazel

100

32.3

59.9

7/3.30

9.9

165

Pine

-

38.7

71.7

7/3.61

10.83

197.7

-

-

45.2

84.1

7/3.91

11.73

231.6

Willow

150

48.4

89.8

7/4.04

12.12

247.5

-

175

51.6

96.5

7/4.19

12.57

266.2

-

300

58.1

108.8

7/4.45

13.35

299.8

Oak

-

64.5

118.9

7/4.65

13.95

327.8


 

 

Code

AL Nominal Area

Cu Nominal Area Equivalent

 

Total Area

 

Stranding

Overall Diameter

 

Weight

 

mm2

mm2

mm2

No.×mm

mm

kg/km

-

-

80.6

118.8

19/2.82

14.1

327.6

Mulberry

-

96.8

151.1

19/3.18

15.9

416.7

Ash

-

113

180.7

19/3.48

17.4

498.1

Elm

-

129

211

19/3.76

18.8

582.1

Poplar

-

145

239

37/2.87

20.09

658.8

-

-

161

270.8

37/3.05

21.35

746.7

Sycamore

-

194

303

37/3.23

22.61

834.9

Upas

-

226

362.1

37/3.53

24.71

998.6

-

-

258

421.8

37/3.81

26.47

1163

Yew

-

-

479.9

37/4.06

28.42

1323

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

BS En 50182

 

Code

 

Stranding

Nominal Area

Overall Diameter

 

Weight

Rated Strength

Electrical Resistance

Current Rating*

 

No.×mm

mm2

mm

kg/km

KN

Ω/Km

A

Box

7/1.85

18.8

5.55

51.4

5.55

1.748

87

Acacia

7/2.08

23.8

6.24

64.9

7.02

1.3828

101

Almond

7/2.34

30.1

7.02

82.2

8.88

1.0926

116

Cedar

7/2.54

35.5

7.62

96.8

10.46

0.9273

129

Deodar

7/2.77

42.2

8.31

115.2

12.44

0.7797

143

Fir

7/2.95

47.8

8.85

130.6

14.11

0.6875

155

Hazel

7/3.30

59.9

9.9

163.4

17.66

0.5494

178

Pine

7/3.61

71.6

10.83

195.6

21.14

0.4591

199

Holly

7/3.91

84.1

11.73

229.5

24.79

0.3913

219

Willow

7/4.04

89.7

12.12

245

26.47

0.3665

228

 

 

Code

 

Stranding

Nominal Area

Overall Diameter

 

Weight

Rated Strength

Electrical Resistance

Current Rating*

 

No.×mm

mm2

mm

kg/km

KN

Ω/Km

A

Oak

7/4.65

118.9

13.95

324.5

35.07

0.2767

272

Mulberry

19/3.18

150.9

15.9

414.3

44.52

0.2192

314

Ash

19/3.48

180.7

17.4

496.1

53.31

0.183

351

Elm

19/3.76

211

18.8

579.2

62.24

0.1568

386

Poplar

37/2.87

239.4

20.09

659.4

70.61

0.1387

416

Sycamore

37/3.23

303.2

22.61

835.2

89.4

0.1095

480

Upas

37/3.53

362.1

24.71

997.5

106.82

0.0917

535

Yew

37/4.06

479

28.42

1319.6

141.31

0.0693

633

Totara

37/4.14

498.1

28.98

1372.1

146.93

0.0666

648

Rubus

61/3.50

586.9

31.5

1622

173.13

0.0567

714

Sorbus

61/3.71

659.4

33.39

1822.5

194.53

0.0505

764

Araucaria

61/4.14

821.1

37.26

2269.4

242.24

0.0406

868

Redwood

61/4.56

996.2

41.04

2753.2

293.88

0.0334

970

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

iEC 60189

 

Code

 

Nominal Area

 

Stranding

Overall Diameter

 

Weight

Rated Strength

Electrical Resistance

Current Rating*

 

mm2

No.×mm

mm

kg/km

KN

Ω/Km

A

16

18.4

7/1.83

5.49

50.4

5.43

1.7896

86

25

28.8

7/2.29

6.87

78.7

8.49

1.1453

113

40

46

7/2.89

8.67

125.9

13.58

0.7158

151

63

72.5

7/3.63

10.89

198.3

21.39

0.4545

200

100

115

19/2.78

13.9

316.3

33.95

0.2877

266

125

144

19/3.1

15.5

395.4

42.44

0.2302

305

160

184

19/3.51

17.55

506.1

54.32

0.1798

355

 

Code

 

Nominal Area

 

Stranding

Overall Diameter

 

Weight

Rated Strength

Electrical Resistance

Current Rating*

 

mm2

No.×mm

mm

kg/km

KN

Ω/Km

A

200

230

19/3.93

19.65

632.7

67.91

0.1439

407

250

288

19/4.39

21.95

790.8

84.88

0.1151

466

315

363

37/3.53

24.71

998.9

106.95

0.0916

535

400

460

37/3.98

27.86

1268.4

135.81

0.0721

618

450

518

37/4.22

29.54

1426.9

152.79

0.0641

663

500

575

37/4.45

31.15

1585.5

169.76

0.0577

706

560

645

61/3.67

33.03

1778.4

190.14

0.0516

755

630

725

61/3.89

35.01

2000.7

213.9

0.0458

809

710

817

61/4.13

37.17

2254.8

241.07

0.0407

866

800

921

61/4.38

39.42

2540.6

271.62

0.0361

928

900*

1036

91/3.81

41.91

2861.1

305.58

0.0321

992

1000*

1151

91/4.01

44.11

3179

339.53

0.0289

1051

1120*

1289

91/4.25

46.75

3560.5

380.27

0.0258

1118

1250*

1439

91/4.49

49.39

3973.7

424.41

0.0231

1185

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.

ASTm B 399/B 399m

 

Nominal Area

 

Stranding

Overall Diameter

 

Weight

Rated Strength

Electrical Resistance

Current Rating*

AWG&MCM

mm2

No.×mm

mm

kg/km

KN

Ω/Km

A

6

13.2

7/1.55

4.65

36.2

4.18

2.5361

69

4

21.1

7/1.96

5.88

57.9

6.69

1.586

93

2

33.5

7/2.47

7.41

92

10.6

0.9987

123

0

53.5

7/3.12

9.36

146.8

17

0.62592

165

2/0

67.3

7/3.50

10.5

184.8

20.4

0.49738

190

3/0

84.9

7/3.93

11.79

233

25.7

0.3945

219

 

 

Nominal Area

 

Stranding

Overall Diameter

 

Weight

Rated Strength

Electrical Resistance

Current Rating*

AWG&MCM

mm2

No.×mm

mm

kg/km

KN

Ω/Km

A

4/0

107

7/4.42

13.26

294.7

32.5

0.31188

253

250

126

19/2.91

14.55

346.7

38.8

0.26509

280

300

152

19/3.19

15.95

416.7

46.6

0.22059

313

350

178

19/3.45

17.25

487.3

52

0.1886

345

400

203

19/3.69

18.45

557.5

59.5

0.16486

375

450

228

19/3.91

19.55

626

66.8

0.14683

402

500

253

19/4.12

20.6

695

74.2

0.13224

429

550

279

37/3.10

21.7

766.2

83.9

0.11995

455

600

303

37/3.23

22.61

831.9

91

0.11049

478

650

330

37/3.37

23.59

905.5

94.9

0.1015

504

700

354

37/3.49

24.43

971.2

101

0.09464

525

750

381

37/3.62

25.34

1045

109

0.08796

549

800

404

37/3.73

26.11

1109

116

0.08285

569

900

456

37/3.96

27.72

1250

131

0.07351

612

1000

508

37/4.18

29.26

1393

146

0.06597

653

1250

631

61/3.63

32.67

1732

179

0.05306

743

1500

759

61/3.98

35.82

2082

215

0.04414

827

1750

886

61/4.30

38.7

2431

251

0.03781

904

(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.


din 48201 Part 6

Nominal Area

 

Stranding

 

Overall Diameter

 

Weight

 

Rated Strength

 

Electrical Resistance

 

Current Rating*

Nominal

Teorical

mm2

mm2

No.×mm

mm

kg/km

KN

Ω/Km

A

16

15.89

7/1.70

5.1

43

4.44

2.0742

78

25

24.25

7/2.10

6.3

66

6.77

1.3593

102

35

34.36

7/2.50

7.5

94

9.6

0.9591

126

50

49.48

7/3.00

9

135

13.82

0.666

158

50

48.35

19/1.80

9

133

13.5

0.6849

156

70

65.81

19/2.10

10.5

181

18.38

0.5032

189

95

93.27

19/2.50

12.5

256

26.05

0.3551

234

120

116.99

19/2.80

14

322

32.68

0.2831

269

150

147.11

37/2.25

15.8

406

41.09

0.2256

309

185

181.62

37/2.50

17.5

500

50.73

0.1828

352

240

242.54

61/2.25

20.3

670

67.74

0.1371

420

300

299.43

61/2.50

22.5

827

83.63

0.111

477

400

400.14

61/2.89

26

1104

111.76

0.0831

568

500

499.83

61/3.23

29.1

1379

139.6

0.0665

649

625*

626.2

91/2.96

32.6

1732

174.9

0.0531

742

800*

802.09

91/3.35

36.9

2218

224.02

0.0415

857

1000*

999.71

91/3.74

41.1

2767

279.22

0.0333

971

* The items marked with “*” are not in our current product range and the details are for information only.
(*) Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.


▓ TECHniCAl dATA

 

Code

Al nominal Area

 

maximum resistance dC at 20º

Current rating

Temperate

Tropical

 

mm2

Ω / km

Ω / 1000ft

Amp

Amp

-

-

2.87

0.873

90

73

Box

-

1.79

0.544

121

98

Acacia

-

1.4

0.426

140

114

Almond

25

1.11

0.339

162

131

Ceda

30

0.944

0.288

180

145

-

40

0.794

0.242

200

162

Fir

50

0.7

0.213

217

175

Hazel

100

0.559

0.17

250

201

Pine

-

0.467

0.142

279

224

-

-

0.398

0.121

309

247

Willow

150

0.373

0.114

322

258

-

175

0.347

0.106

337

270

-

300

0.308

0.0938

343

290

Oak

-

0.282

0.0859

384

307

-

-

0.282

0.086

385

307

Mulberry

-

0.222

0.0676

448

356

Ash

-

0.185

0.0565

501

398

Elm

-

0.159

0.048

553

438

Poplar

-

0.14

0.0427

598

473

-

-

0.124

0.0337

647

511

Sycamore

-

0.111

0.0377

694

547

Upas

-

0.0925

0.0282

776

610

-

-

0.0794

0.0242

854

669

Yew

-

0.0698

0.0213

925

723