Bus Cables

Bus Cables

Profibus L2-Drag Chain(Track)

Profibus L2-Drag Chain(Track)

Application:

This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell

and field area. For the information exchange between different automation systems as well as for

communication with the connected decentralized field units, serial field bus systems are used. The above

mentioned types are suitable for drag chains (stranded).

Construction:

Type/Area of Application :Drag Chain Applications

Cable Construction:1x2x0.64 mm (stranded)

Inner Conductor Diameter:Copper, bare (AWG 24/19)

Conductor Insulation:Foam-skin-PE

Conductor Colors:Red, green

Stranding Element:2 conductors + 2 fillers stranded together

Shielding 1:Polyester foil over stranded bundle

Shielding 2:Polyester foil, aluminum-lined

Total Shielding:Cu braid, tinned

Outer Jacket Material:PUR

Outer Diameter:8.0 mm ± 0.4 mm

Outer Jacket Color:Violet

Electrical Data:

Characteristic Impedance@3-20MHz 150 Ω ± 10 Ω
Conductor Resistance 82.0 Ohm/km max.
Insulation Resistance 1.00 GOhm x km min.
Mutual Capacitance@1KHz 30.0 nF/km nom.
Working Voltage  Max: 250 V
Test Voltage 1.5 kV
Attenuation 9.6 kHz 3.0 dB/km
38.4 kHz 5.0 dB/km
4.0 MHz 25.0 dB/km
16.0 MHz 52.0 dB/km

Technical Data:

Weight:approximately 65.0 kg/km

Min. Bending Radius (Laying):7.5 x OD mm

Operating Temp.Range, min.:-40 °C

Operating Temp.Range, max.:+70 °C