Profibus L2 UL FT4
Application:
This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell
and field area. For the information exchange between different automation systems as well as for
communication with the connected decentralized field units, serial field bus systems are used. The type
described here is suitable for the installation in areas where the FT4 standard (special fire standard “vertical
tray”) according to UL/CSA applies. For this purpose the line was equipped with a special outer PVC jacket.
Construction:
Type/Area of Application :Fixed Installation,Indoor
Cable Construction:1x2x0.64 mm
Inner Conductor Diameter 1:Copper, bare (AWG 22/1)
Conductor Insulation:Foam-Skin-PE
Conductor Colors 1:Red, green
Stranding Element:2 conductors + 2 fillers stranded together
Shielding 1:Polyester foil over stranded bundle
Shielding 2:Polyester foil, aluminum lined
Total Shielding:Copper braid, tinned
Drain wire:Yes
Outer Jacket Material:PVC
Outer Diameter:8.0 mm ± 0.4 mm
Outer Jacket Color :Violet
Electrical Data:
Characteristic Impedance@ -20MHz | 150 Ω ± 10 Ω | ||||
---|---|---|---|---|---|
Conductor Resistance | 55.0 Ohm/km max. | ||||
Insulation Resistance | 1.00 GOhm x km min. | ||||
Mutual Capacitance@1KHz | 30.0 nF/km nom. | ||||
Working Voltage | Max: 250 V | ||||
Test Voltage | 1.5 KV | ||||
Attenuation | 9.6 | kHz | < | 2.5 | dB/km |
38.4 | kHz | < | 4.0 | dB/km | |
4.0 | MHz | < | 22.0 | dB/km | |
16.0 | MHz | < | 45.0 | dB/km |
Technical Data:
Weight:approximately 66.0 kg/km
Min. Bending Radius for Laying :15 x OD mm
Operating Temperature Range, min.:-40 °C
Operating Temperature Range, max.:+70 °C