600/1000V Mica+XLPE Insulated, LSZH Sheathed Power Cables (2-4 cores)
FFX400 1mRZ1-R (CU/MGT+XLPE/LSZH 600/1000V Class 2)
FFX400 1mRMZ1-R (CU/MGT+XLPE/LSZH/SWA/LSZH 600/1000V Class 2)
APPLICATION
This cable is designed for areas where the integrity of the electrical properties circuit is critical in maintaining
power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire
alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and
high-rise buildings.
STANDARDS
Basic design to IEC 60502-1/BS 7846
FIRE PERFORMANCE
Circuit Integrity | IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1); BS 7846-(F2) |
---|---|
System circuit integrity | DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332- 3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2- 4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Mica glass tape covered by extruded cross-linked XLPE compound
Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
Inner Sheath(optional): Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
rmouring(optional): Galvanized steel wire armour
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound
type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation Colour
2 - Core: (Brown & Blue)
3 - Core: (Brown, Black & Grey)
4 - Core: (Brown, Black, Grey & Blue)
Sheath Colour
Orange (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 8 x Overall Diameter (unarmoured cable)
10 x Overall Diameter (armoured cable)
Electrical PROPERTIES
Dielectric test:3500 V r.m.s. x 5’ (core/core)
Insulation resistance:1000 MΩ x km (at 20°C)
Short circuit temperature :250°C
CONSTRUCTION PARAMETERS
Conductor | FFX400 1mRZ1-R | FFX400 1mRMZ1-R | ||||||
---|---|---|---|---|---|---|---|---|
Unarmoured Cable | Armoured Cable | |||||||
Nominal Area | No./Nominal Diameter of Strands | Dia. of Conductor | Nominal Insulation Thickness | Nominal Overall Diameter | Approx. Weight | Nominal Overall Diameter | Approx. Weight | |
mm2 | No./mm | mm | mm | mm | kg/km | mm | kg/km | |
2-CORE | ||||||||
1.5 | 7/0.53 | 1.59 | 0.7 | 12.2 | 150 | 15.3 | 390 | |
2.5 | 7/0.67 | 2.01 | 0.7 | 12.6 | 180 | 16.5 | 450 | |
4 | 7/0.85 | 2.55 | 0.7 | 14.7 | 250 | 17.6 | 525 | |
6 | 7/1.04 | 3.12 | 0.7 | 16.2 | 290 | 18.8 | 620 | |
10 | 7/1.35 | 4.05 | 0.7 | 17.1 | 450 | 21 | 800 | |
16 | 7/1.70 | 5.1 | 0.7 | 19.2 | 550 | 23 | 1100 | |
25 | 7/2.14 | 6.42 | 0.9 | 20 | 680 | 27 | 1480 | |
35 | 19/1.53 | 7.65 | 0.9 | 22 | 940 | 30 | 2000 | |
50 | 19/1.78 | 8.9 | 1 | 24 | 1250 | 33 | 2450 | |
70 | 19/2.14 | 10.7 | 1.1 | 27 | 1700 | 37 | 3200 | |
95 | 19/2.52 | 12.6 | 1.1 | 31 | 2300 | 42 | 4350 | |
120 | 37/2.03 | 14.21 | 1.2 | 36 | 3150 | 48 | 6500 | |
3-CORE | ||||||||
1.5 | 7/0.53 | 1.59 | 0.7 | 12.3 | 170 | 16.5 | 420 | |
2.5 | 7/0.67 | 2.01 | 0.7 | 13.8 | 200 | 17 | 500 | |
4 | 7/0.85 | 2.55 | 0.7 | 15.2 | 300 | 18.5 | 600 | |
6 | 7/1.04 | 3.12 | 0.7 | 16.8 | 380 | 19.8 | 785 | |
10 | 7/1.35 | 4.05 | 0.7 | 18 | 550 | 22.6 | 1030 | |
16 | 1/1.70 | 5.1 | 0.7 | 21 | 760 | 25 | 1370 | |
25 | 7/2.14 | 6.42 | 0.9 | 22 | 960 | 29 | 1900 | |
35 | 19/1.53 | 7.65 | 0.9 | 24 | 1300 | 32 | 2300 | |
50 | 19/1.78 | 8.9 | 1 | 28 | 1700 | 35 | 2900 | |
70 | 19/2.14 | 10.7 | 1.1 | 31 | 2400 | 40 | 4000 | |
95 | 19/2.52 | 12.6 | 1.1 | 36 | 3250 | 45 | 5400 | |
120 | 37/2.03 | 14.21 | 1.2 | 38 | 4000 | 49 | 6450 | |
150 | 37/2.25 | 15.75 | 1.4 | 42 | 5000 | 55 | 8200 | |
185 | 37/2.52 | 17.64 | 1.6 | 47 | 6100 | 60 | 9800 | |
240 | 61/2.25 | 20.25 | 1.7 | 52 | 8000 | 68 | 12300 | |
300 | 61/2.52 | 22.68 | 1.8 | 59 | 9850 | 74 | 14800 | |
400 | 61/2.85 | 25.65 | 2 | 63 | 13000 | 83 | 17600 | |
4-CORE | ||||||||
1.5 | 7/0.53 | 1.59 | 0.7 | 14.3 | 210 | 16 | 475 | |
2.5 | 7/0.67 | 2.01 | 0.7 | 15.2 | 270 | 17.8 | 570 | |
4 | 7/0.85 | 2.55 | 0.7 | 17.2 | 380 | 19.8 | 690 | |
6 | 7/1.04 | 3.12 | 0.7 | 19 | 440 | 21 | 940 | |
10 | 7/1.35 | 4.05 | 0.7 | 20.6 | 670 | 23.3 | 1200 | |
16 | 1/1.70 | 5.1 | 0.7 | 23.6 | 820 | 26.5 | 1400 | |
25 | 7/2.14 | 6.42 | 0.9 | 26 | 1320 | 30.5 | 2400 | |
35 | 19/1.53 | 7.65 | 0.9 | 29 | 1730 | 34 | 2800 | |
50 | 19/1.78 | 8.9 | 1 | 32 | 2300 | 38 | 3500 | |
70 | 19/2.14 | 10.7 | 1.1 | 38 | 3180 | 44 | 5300 | |
95 | 19/2.52 | 12.6 | 1.1 | 41.9 | 4370 | 48.5 | 6700 | |
120 | 37/2.03 | 14.21 | 1.2 | 44 | 5400 | 54 | 8500 | |
150 | 37/2.25 | 15.75 | 1.4 | 50.8 | 6500 | 59 | 10000 | |
185 | 37/2.52 | 17.64 | 1.6 | 55 | 8200 | 64.5 | 12200 | |
240 | 61/2.25 | 20.25 | 1.7 | 60.5 | 10600 | 74 | 15400 | |
300 | 61/2.52 | 22.68 | 1.8 | 68.5 | 13200 | 82 | 19500 | |
400 | 61/2.85 | 25.65 | 2 | 76 | 17000 | 92 | 25500 |
ElectricAl PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
FFX400 1mRZ1-R
Current-Carrying Capacities (Amp)
Nominal Cross Section Area | Reference Method 4 (enclosed in an conduit insulated wall etc) | Reference Method 3 | Reference Method 1 (clipped direct) | Reference Method 11 | |||
---|---|---|---|---|---|---|---|
(enclosed in conduit on a wall or ceiling, or in trunking) | (on a perforated cable tray), or Reference Method 13 (free air) | ||||||
one 3-core cable or one 4-core cable 3-phase a.c. | one 2-core cable single phase a.c. or d.c. | one 3-core cable or one 4-core cable 3-phase a.c. | one 2-core cable single phase a.c. or d.c. | one 3-core cable or one 4-core cable 3-phase a.c. | one 2-core | one 3-core | |
cable singlephase | cable or one | ||||||
a.c. or | 4-core cable | ||||||
d.c. | 3-phase a.c. | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
mm2 | A | A | A | A | A | A | A |
1.5 | 16.5 | 22 | 19.5 | 24 | 22 | 26 | 23 |
2.5 | 22 | 30 | 26 | 33 | 30 | 36 | 32 |
4 | 30 | 40 | 35 | 45 | 40 | 49 | 42 |
6 | 38 | 51 | 44 | 58 | 52 | 63 | 54 |
10 | 51 | 69 | 60 | 80 | 71 | 86 | 75 |
16 | 68 | 91 | 80 | 107 | 96 | 115 | 100 |
25 | 89 | 119 | 105 | 138 | 119 | 149 | 127 |
35 | 109 | 146 | 128 | 171 | 147 | 185 | 158 |
50 | 130 | 175 | 154 | 209 | 179 | 225 | 192 |
70 | 164 | 221 | 194 | 269 | 229 | 289 | 246 |
95 | 197 | 265 | 233 | 328 | 278 | 352 | 298 |
120 | 227 | 305 | 268 | 382 | 322 | 410 | 346 |
150 | 259 | 334 | 300 | 441 | 371 | 473 | 399 |
185 | 295 | 384 | 340 | 506 | 424 | 542 | 456 |
240 | 346 | 459 | 398 | 599 | 500 | 641 | 538 |
300 | 396 | 532 | 455 | 693 | 576 | 741 | 621 |
400 | - | 625 | 536 | 803 | 667 | 865 | 741 |
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area | 2-core cable d.c. | 2-core cable single-phase a.c | 3-core or 4-core cable 3-phase a.c. | ||||
---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | ||||
mm2 | mV/A/m | mV/A/m | mV/A/m | ||||
1.5 | 31 | 31 | 27 | ||||
2.5 | 19 | 19 | 16 | ||||
4 | 12 | 12 | 10 | ||||
6 | 7.9 | 7.9 | 6.8 | ||||
10 | 4.7 | 4.7 | 4 | ||||
16 | 2.9 | 2.9 | 2.5 | ||||
r | x | z | r | x | z | ||
25 | 1.85 | 1.85 | 0.16 | 1.9 | 1.6 | 0.14 | 1.65 |
35 | 1.35 | 1.35 | 0.155 | 1.35 | 1.15 | 0.135 | 1.15 |
50 | 0.98 | 0.99 | 0.155 | 1 | 0.86 | 0.135 | 0.87 |
70 | 0.67 | 0.67 | 0.15 | 0.69 | 0.59 | 0.13 | 0.6 |
95 | 0.49 | 0.5 | 0.15 | 0.52 | 0.43 | 0.13 | 0.45 |
120 | 0.39 | 0.4 | 0.145 | 0.42 | 0.34 | 0.13 | 0.37 |
150 | 0.31 | 0.32 | 0.145 | 0.35 | 0.28 | 0.125 | 0.3 |
185 | 0.25 | 0.26 | 0.145 | 0.29 | 0.22 | 0.125 | 0.26 |
240 | 0.195 | 0.2 | 0.14 | 0.24 | 0.175 | 0.125 | 0.21 |
300 | 0.155 | 0.16 | 0.14 | 0.21 | 0.14 | 0.12 | 0.185 |
400 | 0.12 | 0.13 | 0.14 | 0.19 | 0.115 | 0.12 | 0.165 |
FFX400 1mRMZ1-R
Current-Carrying Capacities (Amp)
Nominal Cross Section Area | Reference Method 1 (clipped direct) | Reference Method 11 (on a perforated horizontal cable tray or Reference Method 13 [free air] ) | In single-way ducts | Laid direct in ground | ||||
---|---|---|---|---|---|---|---|---|
one 2-core cable single phase a.c. or d.c. | one 3-core or 4-core cable 3-phase a.c. | one 2-core cable single phase a.c. or d.c. | one 3-core or 4-core cable 3-phase a.c. | one 2-core cable single phase a.c. or d.c. | one 3-core or 4-core cable 3-phase a.c. | one 2-core cable single phase a.c. or d.c. | one 3-core or 4-core cable 3-phase a.c. | |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
mm2 | A | A | A | A | A | A | A | A |
1.5 | 27 | 23 | 29 | 25 | - | 23 | - | 28 |
2.5 | 36 | 31 | 39 | 33 | - | 30 | - | 36 |
4 | 49 | 42 | 52 | 44 | - | 40 | - | 48 |
6 | 62 | 53 | 66 | 56 | - | 50 | - | 60 |
10 | 85 | 73 | 90 | 78 | - | 65 | - | 80 |
16 | 110 | 94 | 115 | 99 | 115 | 94 | 140 | 115 |
25 | 146 | 124 | 152 | 131 | 145 | 125 | 180 | 150 |
35 | 180 | 154 | 188 | 162 | 175 | 150 | 215 | 180 |
50 | 219 | 187 | 228 | 197 | 210 | 175 | 255 | 215 |
70 | 279 | 238 | 291 | 251 | 260 | 215 | 315 | 265 |
95 | 338 | 289 | 354 | 304 | 310 | 260 | 380 | 315 |
120 | 392 | 335 | 410 | 353 | 355 | 300 | 430 | 360 |
150 | 451 | 386 | 472 | 406 | 400 | 335 | 480 | 405 |
185 | 515 | 441 | 539 | 463 | 455 | 380 | 540 | 460 |
240 | 607 | 520 | 636 | 546 | 520 | 440 | 630 | 530 |
300 | 698 | 599 | 732 | 628 | 590 | 495 | 700 | 590 |
400 | 787 | 673 | 847 | 728 | 660 | 560 | 790 | 670 |
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area | 2-core cable d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | 2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | ||||
---|---|---|---|---|---|---|---|---|---|
In ducts or in ground | In ducts or in ground | ||||||||
1 | 2 | 3 | 4 | 5 | 6 | ||||
mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||
1.5 | 31 | 31 | 27 | 31 | 25 | ||||
2.5 | 19 | 19 | 16 | 19 | 15 | ||||
4 | 12 | 12 | 10 | 12 | 9.7 | ||||
6 | 7.9 | 7.9 | 6.8 | 7.9 | 6.5 | ||||
10 | 4.7 | 4.7 | 4 | 4.7 | 3.9 | ||||
16 | 2.9 | 2.9 | 2.5 | 2.9 | 2.6 | ||||
r | x | z | r | x | z | ||||
25 | 1.85 | 1.35 | 0.16 | 1.9 | 1.6 | 0.14 | 1.65 | 1.9 | 1.6 |
35 | 1.35 | 1.35 | 0.155 | 1.35 | 1.15 | 0.135 | 1.15 | 1.35 | 1.2 |
50 | 0.98 | 0.99 | 0.155 | 1 | 0.86 | 0.135 | 0.87 | 1 | 0.87 |
70 | 0.67 | 0.67 | 0.15 | 0.69 | 0.59 | 0.13 | 0.6 | 0.69 | 0.61 |
95 | 0.49 | 0.5 | 0.15 | 0.52 | 0.43 | 0.13 | 0.45 | 0.52 | 0.45 |
120 | 0.39 | 0.4 | 0.145 | 0.42 | 0.34 | 0.13 | 0.37 | 0.42 | 0.36 |
150 | 0.31 | 0.32 | 0.145 | 0.35 | 0.28 | 0.125 | 0.3 | 0.35 | 0.3 |
185 | 0.25 | 0.26 | 0.145 | 0.29 | 0.22 | 0.125 | 0.26 | 0.29 | 0.25 |
240 | 0.195 | 0.2 | 0.14 | 0.24 | 0.175 | 0.125 | 0.21 | 0.24 | 0.21 |
300 | 0.155 | 0.16 | 0.14 | 0.21 | 0.14 | 0.12 | 0.185 | 0.21 | 0.19 |
400 | 0.12 | 0.13 | 0.14 | 0.19 | 0.115 | 0.12 | 0.165 | 0.19 | 0.18 |
Note : r = conductor resistance at operating temperature
x = reactance
z = impedance