Marine Cables
MariTox Marine Flame Retardant Medium Voltage Cables MariTox Marine Flame Retardant Power & Control Cables MariFlex Marine Fire Resistant Power & Control Cables other

Water Blocked

P2 or P2/P9 RFOU/TFOU 3.6/6KV

Applications

Marine cables are partially water blocked, flame retardant, low smoke, halogen free and mud resistant, used for

fixed installation for medium voltage power.

Standards

IEC 60092-353

IEC 60092-360

IEC 60332-1

IEC 60332-3-22

IEC 60754-1,2

IEC 61034-1,2

NEK 606

VG 95218 part 29 

Water Blocked P2 or P2/P9 RFOU/TFOU 3.6/6KV

Construction

Electrical Characteristics

Ambient Temperature Correction Factors

Mechanical and Thermal Properties

Bending Radius :15×OD (during installation); 9×OD (fixed installed).

Temperature Range : -20℃ ~ +90℃

Dimensions and Weight

Construction No. of cores×Cross section

mm²

Nominal Insulation Thickness

mm

Nominal BeddingThickness

mm

NominalInner Sheath Thickness

mm

NominalOuter Sheath Thickness

mm

Nominal Overall Diameter

mm

Nominal Weight

kg/km

1×16 2.5 1.4 1.1 1 24.8±2 819
1×25 2.5 1.5 1.1 1.2 26.4±2 1071
1×35 2.5 1.5 1.2 1.2 27.5±2 1213
1×50 2.5 1.6 1.2 1.2 28.7±2 1386
1×70 2.5 1.6 1.3 1.2 30.6±2 1675
1×95 2.5 1.7 1.3 1.4 32.8±2 2000
1×120 2.5 1.8 1.4 1.4 34.6±2 2347
1×150 2.5 1.8 1.4 1.4 36.3±2 2678
1×185 2.5 1.9 1.5 1.4 38.0±2 3166
1×240 2.6 2 1.5 1.6 42.0±2 3911
1×300 2.8 2.1 1.6 1.6 45.5±2 4856
1×400 3 2.2 1.7 1.6 49.8±2 5691
1×500 3.2 2.4 1.8 1.6 54.0±2 6941
1×630 3.2 2.5 1.9 1.6 58.3±2 8579
3×16 2.5 2.2 1.6 1 46.9±2 3077
3×25 2.5 2.3 1.7 1.2 47.8±2 3560
3×35 2.5 2.4 1.8 1.2 50.0±2 4011
3×50 2.5 2.5 1.9 1.2 53.3±2 4720
3×70 2.5 2.7 2 1.2 57.2±2 5864
3×95 2.5 2.8 2.1 1.4 61.7±2 7103
3×120 2.5 3 2.2 1.4 66.3±2 8573
3×150 2.5 3.1 2.3 1.4 70.2±2 9970
3×185 2.5 3.3 2.4 1.4 78.6±2 11193
3×240 2.6 3.5 2.5 1.6 85.5±2 12243
3×300 2.8 3.8 2.7 1.6 92.5±2 13587