Medium Voltage Cables
Medium Voltage Cables to BS 6622 Medium Voltage Cables to IEC 60502 Medium Voltage Cables to VDE 0276

Medium Voltage Cables to JIS C 3606-2003

Three Core Cables

Application

This product is used for an underground distribution cable for the lead-out parts of substations of general power

distribution lines including high-capacity power distribution, cable tunnels, pipelines, directly embedded types,

raising parts of telephone poles, etc.

Standards

JIS C 3606-2003 (6600V)

Construction

Conductor: Plain annealed copper with JCS C 3102.

Conductor Screen: The conductor screen consists of an extruded layer of non metallic, semi-conducting

compound firmly bonded to the insulation to exclude all air voids.

Insulation: XLPE.

Insulation Screen: The insulation screen consists of an extruded layer of non metallic, semi- conducting

compound extruded over the insulation. The extruded semi-conducting layer shall consist of bonded  or cold

strippable semi-conducting compound  capable of removal  for jointing or terminating. As an option, a semi-

conducting tape may be applied over the extruded semi-conducting layer as a bedding for the metallic layer. The

minimum thickness is 0.5 mm. The screen is tightly fitted to the insulation to exclude all air voids and can be

easily hand stripped on site.

Metallic Sreen: By sufficiently winding of a soft copper tape on an external semiconductive layer, each core shall

be shielded,the tape is wound with overlapping about one-sixth of its width or the equivalent of that.

Over Sheath: Black, PVC or PE.

Identification of wire cores:Wire core identification shall be performed with 3 colors, that is, white, red and

blue.

PHYSICAL PROPERTIES:

Operating Temperature: up to 120°C

Cold Resistant: -15 ± 0.5 °C

Three Core 6600V (Test Voltage=17KV)

Dimensional Data

Nom.Cross- Section Area

Nom. Insulation Thickness

Nom. Sheath Thickness

Approx. Overall Diameter

Approx.
Weight

CV

CE

CE/F

mm²

mm

mm

mm

kg/km

8

4.0

2.4

32

1180

1080

1150

14

4.0

2.5

34

1480

1370

1450

22

4.0

2.5

37

1780

1560

1710

38

4.0

2.7

41

2430

2290

2390

60

4.0

2.9

46

3280

3110

3230

100

4.0

3.1

52

4670

4470

4610

150

4.0

3.3

58

6420

5870

6240

200

4.5

3.6

66

8330

8000

8220

250

4.5

3.8

71

10020

9390

9810

325

4.5

4.0

77

12990

12590

12860

Electrical Data


Nom.Cross- Section Area

Max. Conductor Resistance (20 °C)

 

Min. Insulation Resistance

 

Electrostatic Capacitance

mm²

Ω/km

MΩ-km

µF/ Km

8

2.34

2500

0.21

14

1.34

2500

0.24

22

0.849

2500

0.27

38

0.491

2000

0.32

60

0.311

2000

0.37

100

0.187

1500

0.45

150

0.124

1500

0.52

200

0.0933

1500

0.51

250

0.0754

1500

0.55

325

0.0579

1500

0.61

 

Note:C:XLPE V:Vinyl E:PE F:Flame retardant