Power Cables
PVC Insulated & Sheathed Unarmoured XLPE Insulated PVC/LSOH Sheathed LSOH Insulated Conduit Wires Fire Resistant Medium Voltage

Power Cables

BS 6622 Single Core Armoured 22KV XLPE Stranded Copper Conductors

Construction

cross-sectional area mm2 Minimum average thickness of insulation mm Nominal diameter over insulation
mm
Nominal thickness of PVC bedding
mm
Nominal number and diameter of armoured wires no./mm Nominal thickness of PVC oversheath
mm
Nominal overall diameter of cable mm
50 5.5 21.6 1.2 47/1.6 2 32.7
70 5.5 23.4 1.2 40/2.0 2 35.3
95 5.5 25.1 1.2 43/2.0 2.1 37.2
120 5.5 26.6 1.2 45/2.0 2.1 38.7
150 5.5 27.9 1.2 47/2.0 2.2 40.4
185 5.5 29.7 1.2 49/2.0 2.2 42.2
240 5.5 31.9 1.2 52/2.0 2.3 44.6
300 5.5 34.2 1.3 45/2.5 2.4 48.3
400 5.5 36.9 1.3 48/2.5 2.5 51.2
500 5.5 39.8 1.4 52/2.5 2.6 54.5
630 5.5 43.2 1.4 55/2.5 2.8 58.3
800 Please refer to our technical department for further information
1000

Installation

cross-sectional area mm2 Approximate cable weight kg/m Nominal drum length
m
Minimum bending radius mm Nominal internal diameter of ducts mm
50 1.6 1000 600 100
70 1.9 500 650 100
95 2.3 500 700 100
120 2.6 500 700 100
150 2.9 500 750 100
185 3.4 500 800 100
240 4.0 500 850 100
300 4.9 500 900 100
400 5.8 250 950 100
500 7.0 250 1000 100
630 8.4 250 1050 100
800 Please refer to our technical department for further information
1000

Electrical Performance

cross-sectional area mm2 Maximum DC resistance of conductor at 20 ℃ uohms/m Maximum AC resistance of conductor at 90 ℃ uohms/m Reactance at 50Hz
uohms/m
Impedance at 50Hz uohms/m Maximum Capacitace PF/m Maximum charging current at normal voltage and frequency mA/m
50 387 494 149 515 177 0.71
70 268 343 141 370 200 0.80
95 193 248 133 281 222 0.89
120 153 196 128 234 241 0.96
150 124 159 125 201 257 1.03
185 99.1 128 120 174 280 1.12
240 75.4 98 116 151 307 1.23
300 60.1 80 113 137 336 1.34
400 47 64 109 125 370 1.48
500 36.6 51 106 117 406 1.62
630 28.3 42 102 110 449 1.8
800 Please refer to our technical department for further information
1000

Ratings

Cross-sectional area
mm2
Current Ratings Short circuit ratings
Laid direct in ground
Amps
Drawn into ducts
Amps
Laid in air
Amps
One second short circuit rating of conductor
KA
One second short circuit rating of copper per core
KA
50 220 210 260 6.8 Typically less then 1kA
70 270 260 320 9.8
95 320 300 380 13.3
120 360 340 440 17.2
150 410 370 490 21.2
185 450 400 560 26.6
240 510 450 650 34.9
300 570 490 730 43.8
400 640 530 830 57.3
500 700 570 940 72.3
630 760 610 1050 91.2
800 Please refer to our technical department for further information
1000