Power Cables | ||||||||||||
|
Power Cables
BS 6622 Single Core Unarmoured (Copper Wire Screen) 22KV XLPE Stranded Copper Conductors
Construction
cross-ectional area mmsq | Minimum average thickness of insulation mm | Nominal diameter over insulation mm |
Nominal area of copper wire screen mm |
Nominal average thickness of PVC oversheath mm |
Nominal overall diameter of cable mm |
---|---|---|---|---|---|
50 | 5.5 | 21.6 | 16 | 1.8 | 28.8 |
70 | 5.5 | 23.4 | 16 | 1.9 | 30.6 |
95 | 5.5 | 25.1 | 16 | 1.9 | 32.5 |
120 | 5.5 | 26.6 | 16 | 2.0 | 34.0 |
150 | 5.5 | 27.9 | 16 | 2.0 | 35.5 |
185 | 5.5 | 29.7 | 16 | 2.1 | 37.3 |
240 | 5.5 | 31.9 | 25 | 2.2 | 39.7 |
300 | 5.5 | 34.2 | 25 | 2.2 | 42.2 |
400 | 5.5 | 36.9 | 35 | 2.3 | 45.2 |
500 | 5.5 | 39.8 | 35 | 2.4 | 48.3 |
630 | 5.5 | 43.2 | 35 | 2.5 | 51.9 |
800 | Please refer to our technical department for further information | ||||
1000 |
Installation
cross-sectional area mmsq | Approximate cable weight kg/m | Nominal drum length m |
Minimum bending radius mm | Nominal internal diameter of ducts mm |
---|---|---|---|---|
50 | 1.2 | 1000 | 550 | 100 |
70 | 1.5 | 1000 | 600 | 100 |
95 | 1.8 | 1000 | 600 | 100 |
120 | 2 | 500 | 650 | 100 |
150 | 2.4 | 500 | 650 | 100 |
185 | 2.7 | 500 | 700 | 100 |
240 | 3.4 | 500 | 750 | 100 |
300 | 4.1 | 500 | 800 | 100 |
400 | 5 | 500 | 850 | 100 |
500 | 6.1 | 500 | 900 | 100 |
630 | 7.4 | 250 | 950 | 100 |
800 | Please refer to our technical department for further information | |||
1000 |
Electrical Performance
cross-sectional area mmsq | Maximum DC resistance of conductor at 20 ℃ uohms/m | Maximum AC resistance of conductor at 90 ℃ uohms/m | Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m |
---|---|---|---|---|---|---|
50 | 387 | 494 | 141 | 573 | 177 | 0.71 |
70 | 268 | 343 | 132 | 367 | 200 | 0.80 |
95 | 193 | 248 | 125 | 277 | 222 | 0.89 |
120 | 153 | 196 | 120 | 230 | 241 | 0.96 |
150 | 124 | 159 | 117 | 197 | 257 | 1.03 |
185 | 99.1 | 128 | 112 | 169 | 280 | 1.12 |
240 | 75.4 | 98 | 108 | 145 | 307 | 1.23 |
300 | 60.1 | 80 | 105 | 131 | 336 | 1.34 |
400 | 47 | 64 | 101 | 119 | 370 | 1.48 |
500 | 36.6 | 57 | 98.3 | 110 | 406 | 1.62 |
630 | 28.3 | 42 | 94.9 | 103 | 449 | 1.80 |
800 | Please refer to our technical department for further information | |||||
1000 |
Ratings
Cross-sectional area mmsq |
Current Ratings | Short circuit ratings | |||
---|---|---|---|---|---|
Laid direct in ground Amps |
Drawn into ducts Amps |
Laid in air Amps |
One second short circuit rating of conductor KA |
One second short circuit rating of copper per core KA |
|
50 | 220 | 225 | 260 | 6.8 | 2.6 |
70 | 270 | 270 | 320 | 9.8 | 2.6 |
95 | 320 | 320 | 390 | 13.3 | 2.6 |
120 | 360 | 360 | 445 | 17.2 | 2.6 |
150 | 410 | 405 | 510 | 21.2 | 2.6 |
185 | 460 | 445 | 580 | 26.6 | 2.6 |
240 | 530 | 520 | 680 | 34.9 | 4.3 |
300 | 600 | 570 | 770 | 43.8 | 4.3 |
400 | 690 | 630 | 890 | 57.3 | 5.8 |
500 | 760 | 700 | 1020 | 72.3 | 5.8 |
630 | 850 | 780 | 1160 | 91.2 | 5.8 |
800 | Please refer to our technical department for further information | ||||
1000 |