Power Cables | ||||||||||||
|
Power Cables
BS 6622 Single Core Armoured 33KV XLPE Stranded Copper Conductors
Construction
cross-sectional area mm2 | Minimum average thickness of insulation mm | Nominal diameter over insulation mm |
Nominal thickness of PVC bedding mm |
Nominal number and diameter of armoured wires no./mm | Nominal thickness of PVC oversheath mm |
Nominal overall diameter of cable mm |
---|---|---|---|---|---|---|
50 | 8 | 27.1 | 1.2 | 46/2.0 | 2.2 | 39.4 |
70 | 8 | 28.9 | 1.2 | 48/2.0 | 2.2 | 41.4 |
95 | 8 | 30.6 | 1.2 | 51/2.0 | 2.3 | 43.3 |
120 | 8 | 32.1 | 1.2 | 53/2.0 | 2.3 | 44.8 |
150 | 8 | 33.4 | 1.3 | 44/2.5 | 2.4 | 47.5 |
185 | 8 | 35.2 | 1.3 | 46/2.5 | 2.5 | 49.5 |
240 | 8 | 37.4 | 1.3 | 49/2.5 | 2.5 | 51.7 |
300 | 8 | 39.7 | 1.4 | 52/2.5 | 2.6 | 54.4 |
400 | 8 | 42.4 | 1.4 | 55/2.5 | 2.7 | 57.3 |
500 | 8 | 45.3 | 1.5 | 58/2.5 | 2.8 | 60.6 |
630 | 8 | 48.7 | 1.5 | 62/2.5 | 2.9 | 64.2 |
800 | Please refer to our technical department for further information | |||||
1000 |
Installation
cross-sectional area mm2 | Approximate cable weight kg/m | Nominal drum length m |
Minimum bending radius mm | Nominal internal diameter of ducts mm |
---|---|---|---|---|
50 | 2.1 | 1000 | 850 | 100 |
70 | 2.4 | 500 | 900 | 100 |
95 | 2.7 | 500 | 950 | 100 |
120 | 3.1 | 500 | 950 | 100 |
150 | 3.6 | 500 | 1000 | 100 |
185 | 4.0 | 500 | 1050 | 100 |
240 | 4.7 | 500 | 1100 | 100 |
300 | 5.5 | 500 | 1150 | 100 |
400 | 6.4 | 250 | 1250 | 100 |
500 | 7.6 | 250 | 1300 | 125 |
630 | 9.1 | 250 | 1350 | 125 |
800 | Please refer to our technical department for further information | |||
1000 |
Electrical Performance
cross-sectional area mm2 | Maximum DC resistance of conductor at 20 ℃ uohms/m | Maximum AC resistance of conductor at 90 ℃ uohms/m | Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m |
---|---|---|---|---|---|---|
50 | 387 | 494 | 160 | 578 | 138 | 0.83 |
70 | 268 | 343 | 151 | 374 | 154 | 0.92 |
95 | 193 | 248 | 143 | 285 | 169 | 1.01 |
120 | 153 | 196 | 137 | 239 | 183 | 1.10 |
150 | 124 | 159 | 135 | 207 | 194 | 1.16 |
185 | 99.1 | 128 | 130 | 181 | 210 | 1.26 |
240 | 75.4 | 98 | 125 | 158 | 229 | 1.37 |
300 | 60.1 | 80 | 121 | 144 | 249 | 1.49 |
400 | 47.0 | 64 | 116 | 132 | 273 | 1.64 |
500 | 36.6 | 51 | 113 | 123 | 298 | 1.79 |
630 | 28.3 | 42 | 108 | 115 | 327 | 1.96 |
800 | Please refer to our technical department for further information | |||||
1000 |
Ratings
Cross-sectional area mm2 |
Current Ratings | Short circuit ratings | |||
---|---|---|---|---|---|
Laid in ground Amps |
Drawn into ducts Amps |
Laid in air Amps |
One second short circuit rating of conductor KA |
One second short circuit rating of copper per core KA |
|
50 | 220 | 210 | 260 | 6.8 | Typically less then 1kA |
70 | 270 | 260 | 320 | 9.8 | |
95 | 320 | 300 | 380 | 13.3 | |
120 | 360 | 340 | 440 | 17.2 | |
150 | 410 | 370 | 490 | 21.2 | |
185 | 450 | 400 | 560 | 26.6 | |
240 | 510 | 450 | 650 | 34.9 | |
300 | 570 | 490 | 730 | 43.8 | |
400 | 640 | 530 | 830 | 57.3 | |
500 | 700 | 570 | 940 | 72.3 | |
630 | 760 | 610 | 1050 | 91.2 | |
800 | Please refer to our technical department for further information | ||||
1000 |