Power Cables | ||||||||||||
|
Power Cables
BS 6622 Three Core Armoured 33KV XLPE Stranded Copper Conductors
Construction
cross-sectional area mmsq | Minimum average thickness of insulation mm | Nominal diameter over insulation mm |
Nominal thickness of PVC bedding mm |
Nominal number and diameter of armoured wires no./mm | Nominal thickness of PVC oversheath mm |
Nominal overall diameter of cable mm |
---|---|---|---|---|---|---|
50 | 8 | 27.1 | 1.8 | 60/3.15 | 3.4 | 78.5 |
70 | 8 | 28.9 | 1.8 | 64/3.15 | 3.5 | 82.6 |
95 | 8 | 30.6 | 1.9 | 67/3.15 | 3.6 | 86.7 |
120 | 8 | 32.1 | 2.0 | 70/3.15 | 3.7 | 90.3 |
150 | 8 | 33.4 | 2.0 | 72/3.15 | 3.8 | 93.3 |
185 | 8 | 35.2 | 2.1 | 76/3.15 | 3.9 | 97.6 |
240 | 8 | 37.4 | 2.2 | 80/3.15 | 4.1 | 102.9 |
300 | 8 | 39.7 | 2.3 | 85/3.15 | 4.3 | 108.5 |
400 | 8 | 42.4 | 2.4 | 90/3.15 | 4.5 | 114.9 |
Installation
cross-sectional area mmsq | Approximate cable weight kg/m | Nominal drum length m |
Minimum bending radius mm | Nominal internal diameter of ducts mm |
---|---|---|---|---|
50 | 9.7 | 350 | 1450 | 125 |
70 | 10.7 | 350 | 1500 | 125 |
95 | 12 | 300 | 1600 | 125 |
120 | 13.3 | 250 | 1650 | 150 |
150 | 14.4 | 250 | 1700 | 150 |
185 | 16.1 | 250 | 1800 | 150 |
240 | 18.4 | 250 | 1900 | 150 |
300 | 21 | 250 | 2000 | 150 |
400 | 24.2 | 250 | 2100 | 150 |
Electrical Performance
cross-sectional area mmsq | Maximum DC resistance of conductor at 20 ℃ uohms/m | Maximum AC resistance of conductor at 90 ℃ uohms/m | Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m |
---|---|---|---|---|---|---|
50 | 387 | 494 | 143 | 513 | 142 | 0.85 |
70 | 268 | 343 | 134 | 367 | 159 | 0.95 |
95 | 193 | 248 | 127 | 278 | 175 | 1.05 |
120 | 153 | 196 | 122 | 231 | 189 | 1.13 |
150 | 124 | 159 | 118 | 197 | 201 | 1.21 |
185 | 99.1 | 128 | 114 | 171 | 217 | 1.30 |
240 | 75.4 | 98 | 109 | 146 | 237 | 1.42 |
300 | 60.1 | 80 | 105 | 131 | 258 | 1.55 |
400 | 47.0 | 64 | 102 | 120 | 282 | 1.69 |
Ratings
Cross-sectional area mmsq |
Current Ratings | Short circuit ratings | |||
---|---|---|---|---|---|
Laid in ground Amps |
Drawn into ducts Amps |
Laid in air Amps |
One second short circuit rating of conductor KA |
One second short circuit rating of copper per core KA |
|
50 | 210 | 185 | 225 | 6.8 | Typically less then 1kA |
70 | 255 | 225 | 275 | 9.8 | |
95 | 295 | 260 | 330 | 13.3 | |
120 | 335 | 300 | 380 | 17.2 | |
150 | 375 | 335 | 430 | 21.2 | |
185 | 420 | 380 | 490 | 26.6 | |
240 | 480 | 430 | 570 | 34.9 | |
300 | 530 | 480 | 650 | 43.8 | |
400 | 580 | 530 | 720 | 57.3 |