BS 6622 Single Core Unarmoured (Copper Wire Screened) 6.6kV XLPE Stranded Aiuminium Conductors
Construction
cross-sectional area mm2 | Minimum average thickness of insulation mm | Nominal diameter over insulation mm |
Nominal area of copperwire screen mm2 | Nominal average thickness of PVC oversheath mm |
Nominal overall diameter of cable mm |
---|---|---|---|---|---|
70 | 2.5 | 16.8 | 16.0 | 1.7 | 23.5 |
95 | 2.5 | 18.5 | 16.0 | 1.7 | 25.4 |
120 | 2.5 | 20.0 | 16.0 | 1.8 | 26.9 |
150 | 2.5 | 21.3 | 16.0 | 1.8 | 28.5 |
185 | 2.5 | 23.1 | 16.0 | 1.9 | 30.3 |
240 | 2.6 | 25.5 | 25.0 | 1.9 | 32.9 |
300 | 2.8 | 28.3 | 25.0 | 2.0 | 35.9 |
400 | 3.0 | 31.4 | 35.0 | 2.2 | 39.2 |
500 | 3.2 | 34.7 | 35.0 | 2.6 | 42.8 |
630 | 3.2 | 38.6 | 35.0 | 3.1 | 47.0 |
Installation
cross-sectional area mm2 | Approximate cable weight kg/m | Nominal drum length m |
Minimum bending radius mm | Nominal internal diameter of ducts mm |
---|---|---|---|---|
70 | 0.7 | 1000 | 400 | 100 |
95 | 0.8 | 1000 | 400 | 100 |
120 | 1.0 | 1000 | 450 | 100 |
150 | 1.1 | 500 | 450 | 100 |
185 | 1.3 | 500 | 500 | 100 |
240 | 1.5 | 500 | 500 | 100 |
300 | 1.7 | 500 | 550 | 100 |
400 | 2.2 | 500 | 600 | 100 |
500 | 2.6 | 500 | 650 | 100 |
630 | 3.1 | 300 | 750 | 100 |
Electrical Performance
cross-sectional area mm2 | Maximum DC resistance of conductor at 20 ℃ uohms/m | Maximum AC resistance of conductor at 90 ℃ uohms/m | Reactance at 50Hz uohms/m |
Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m |
---|---|---|---|---|---|---|
70 | 443 | 568 | 111 | 580 | 371 | 0.45 |
95 | 320 | 410 | 109 | 424 | 417 | 0.50 |
120 | 253 | 325 | 105 | 342 | 459 | 0.55 |
150 | 206 | 265 | 103 | 284 | 494 | 0.59 |
185 | 164 | 211 | 99.5 | 233 | 543 | 0.65 |
240 | 125 | 161 | 96.6 | 188 | 583 | 0.70 |
300 | 100 | 130 | 94.7 | 161 | 602 | 0.72 |
400 | 77.8 | 102 | 92.5 | 138 | 627 | 0.75 |
500 | 60.5 | 81.0 | 90.7 | 122 | 654 | 0.79 |
630 | 46.9 | 64.0 | 87.6 | 109 | 737 | 0.87 |
Ratings
Cross-sectional area mm2 |
Current Ratings | Short circuit ratings | |||
---|---|---|---|---|---|
Laid direct in ground Amps |
Drawn into ducts Amps |
Laid in air Amps |
One second short circuit rating of conductor KA |
One second short circuit rating of copper per core KA |
|
70 | 210 | 215 | 240 | 6.3 | 2.6 |
95 | 250 | 255 | 300 | 8.5 | 2.6 |
120 | 280 | 285 | 335 | 11.0 | 2.6 |
150 | 320 | 315 | 380 | 13.5 | 2.6 |
185 | 360 | 350 | 435 | 17.0 | 2.6 |
240 | 415 | 405 | 510 | 22.3 | 4.3 |
300 | 475 | 455 | 600 | 28.0 | 4.3 |
400 | 540 | 510 | 700 | 36.6 | 5.8 |
500 | 610 | 570 | 810 | 46.2 | 5.8 |
630 | 680 | 640 | 930 | 58.3 | 5.8 |