600/1000V TWO-CORE PVC INSULATED ,PVC SHEATHED,ARMOURED CABLE TO BS 6346
Construction
Conductor : Plain annealed copper
Insulation : Flame Retardant PVC Compound
Filler: PVC or Polypropylene yarn
Binder Tape: Polyester (mylar) tape
Bedding: Flame retardant PVC compound
Armouring: Steel wire armored
Sheath: Flame retardant PVC compound
Size of Conductor | Nominal Thickness of Insulation | STEEL WIRE ARMOURED (SWA) CABLE | ||||
---|---|---|---|---|---|---|
Nominal Thickness of Bedding | Nominal Dia. of Armour Wire | Nominal Thickness of Sheath | Approx. Overall Diameter | Approx. Weight | ||
mm2 | mm | mm | mm | mm | mm | kg/km |
1.5 | 0.6 | 0.8 | 0.9 | 1.4 | 12.3 | 290 |
2.5 | 0.7 | 0.8 | 0.9 | 1.4 | 13.6 | 355 |
4 | 0.8 | 0.8 | 0.9 | 1.4 | 15.1 | 445 |
6 | 0.8 | 0.8 | 0.9 | 1.5 | 16.5 | 520 |
10 | 1.0 | 0.8 | 1.25 | 1.6 | 20.1 | 845 |
16 | 1.0 | 0.8 | 1.25 | 1.6 | 21.9 | 1050 |
25 | 1.2 | 1.0 | 1.6 | 1.7 | 23.0 | 1340 |
35 | 1.2 | 1.0 | 1.6 | 1.8 | 24.9 | 1615 |
50 | 1.4 | 1.0 | 1.6 | 1.9 | 27.8 | 2035 |
70 | 1.4 | 1.0 | 1.6 | 1.9 | 30.4 | 2570 |
95 | 1.6 | 1.2 | 2.0 | 2.1 | 35.5 | 3590 |
120 | 1.6 | 1.2 | 2.0 | 2.2 | 38.0 | 4230 |
150 | 1.8 | 1.2 | 2.0 | 2.3 | 41.3 | 4990 |
185 | 2.0 | 1.4 | 2.5 | 2.4 | 46.4 | 6460 |
240 | 2.2 | 1.4 | 2.5 | 2.5 | 55.0 | 8225 |
300 | 2.4 | 1.6 | 2.5 | 2.7 | 66.5 | 10745 |
400 | 2.6 | 1.6 | 2.5 | 2.9 | 73.0 | 12990 |