Power Cables | ||||||||||||
|
Power Cables
600/1000V FOUR-CORE PVC INSULATED, PVC SHEATHED, ARMOURED CABLE TO BS 6346
Construction
Conductor : Plain annealed copper
Insulation : Flame retardant PVC compound
Filler: PVC or Polypropylene yarn
Binder Tape: Polyester (mylar) tape
Bedding: Flame retardant PVC compound
Armouring: Steel wire armored
Sheath: Flame retardant PVC compound
Size of Conductor | Nominal Thickness of Insulation | STEEL WIRE ARMOURED (SWA) CABLE | |||
---|---|---|---|---|---|
Nominal Dia. of Armour Wire | Nominal Thickness of Sheath | Approx. Overall Diameter | Approx. Weight | ||
mm2 | mm | mm | mm | mm | kg/km |
1.5 | 0.6 | 0.9 | 1.4 | 13.5 | 365 |
2.5 | 0.7 | 0.9 | 1.4 | 15 | 455 |
4 | 0.8 | 1.25 | 1.5 | 17.8 | 700 |
6 | 0.8 | 1.25 | 1.5 | 19.2 | 820 |
10 | 1 | 1.25 | 1.6 | 22.8 | 1135 |
16 | 1 | 1.6 | 1.7 | 26.3 | 1685 |
25 | 1.2 | 1.6 | 1.8 | 27.8 | 2150 |
35 | 1.2 | 1.6 | 1.9 | 30.5 | 2650 |
50 | 1.4 | 2 | 2 | 35.4 | 3660 |
70 | 1.4 | 2 | 2.1 | 39.2 | 4735 |
95 | 1.6 | 2 | 2.2 | 44.3 | 6130 |
120 | 1.6 | 2.5 | 2.4 | 49.3 | 7835 |
150 | 1.8 | 2.5 | 2.5 | 53.6 | 9300 |
185 | 2 | 2.5 | 2.6 | 59 | 11375 |
240 | 2.2 | 2.5 | 2.8 | 70 | 14545 |
300 | 2.4 | 3.15 | 3 | 80 | 18670 |
400 | 2.6 | 3.15 | 3.3 | 88 | 22980 |