Submarine Cables
XLPE Insulated AC Medium-voltage Submarine Cable With Fibre Optic Cable
Applications
These submarine cables are used for power transmission to offshore islands, oil platforms or to cross-rivers and
lakes. Cable design based on the mayor national or international standards e.g. VDE, IEC and ICEA or according
to customers design and standards.
Construction
Conductor:Copper conductor, circular stranded compacted, water blocked.
Conductor Screening: Extruded semi-conductive compound.
Insulation: XLPE.
Insulation Screening: Extruded semi-conductive compound.
Screen: Copper wires and copper helix, swelling powder.
Laminated Core Sheath: Aluminium tape bonded to overlaying PE sheath
Fillers: Polypropylene filler.
Fibre-optic Element: Fibre optic cable.
Separator: Binder tapes.
Bedding Layer: Polypropylene strings.
Armour: Galvanized steel wires.
Serving: Hessian tapes, bituminous compound, polypropylene strings.
Electrical Data:
6/10(12) kV
Nominal Cross Section Area | Capacitance | Inductance | Current Rating |
---|---|---|---|
mm² | μF/mm | mH/km | A |
35 | 0.23 | 0.43 | 167 |
50 | 0.26 | 0.41 | 199 |
70 | 0.29 | 0.38 | 241 |
95 | 0.32 | 0.37 | 288 |
120 | 0.35 | 0.35 | 327 |
150 | 0.38 | 0.34 | 363 |
185 | 0.42 | 0.33 | 405 |
240 | 0.47 | 0.32 | 464 |
12/20(24) kV
Nominal Cross Section Area | Capacitance | Inductance | Current Rating |
---|---|---|---|
mm² | μF/mm | mH/km | A |
35 | 0.17 | 0.47 | 171 |
50 | 0.18 | 0.44 | 199 |
70 | 0.20 | 0.41 | 243 |
95 | 0.22 | 0.40 | 292 |
120 | 0.24 | 0.38 | 328 |
150 | 0.26 | 0.37 | 364 |
185 | 0.28 | 0.35 | 408 |
240 | 0.31 | 0.34 | 467 |
18/30(36) kV
Nominal Cross Section Area | Capacitance | Inductance | Current Rating |
---|---|---|---|
mm² | μF/mm | mH/km | A |
50 | 0.14 | 0.48 | 202 |
70 | 0.15 | 0.45 | 245 |
95 | 0.17 | 0.42 | 291 |
120 | 0.18 | 0.41 | 330 |
150 | 0.19 | 0.39 | 366 |
185 | 0.21 | 0.38 | 411 |
240 | 0.23 | 0.36 | 470 |
Dimension and Weight:
6/10(12) kV
Nominal Cross Section Area | Nominal Conductor Diameter | Nominal Insulation Thickness | Nominal Screen Cross Section Area |
Nominal Core Sheath Thickness | Nominal Core Diameter | Nominal Bedding Thickness | Nominal Steel Wire Diameter | Serving Thickness |
Overall Diameter |
Weight |
---|---|---|---|---|---|---|---|---|---|---|
mm² | mm | mm | mm² | mm | mm | mm | mm | mm | mm | kg/m |
35 | 7.0 | 3.4 | 16 | 2.5 | 24 | 2 | 3.15 | 3.5 | 70 | 7.5 |
50 | 8.2 | 3.4 | 16 | 2.5 | 25 | 2 | 3.15 | 3.5 | 73 | 8.2 |
70 | 9.9 | 3.4 | 16 | 2.5 | 27 | 2 | 4.0 | 3.5 | 77 | 9.9 |
95 | 11.5 | 3.4 | 16 | 2.5 | 28 | 2 | 4.0 | 3.5 | 80 | 11.1 |
120 | 13.0 | 3.4 | 16 | 2.5 | 30 | 2 | 4.0 | 3.5 | 84 | 12.2 |
150 | 14.5 | 3.4 | 25 | 2.5 | 31 | 2 | 4.0 | 3.5 | 87 | 13.6 |
185 | 16.1 | 3.4 | 25 | 2.5 | 33 | 2 | 5.0 | 4.0 | 93 | 16.8 |
240 | 18.6 | 3.4 | 25 | 2.5 | 35 | 2 | 5.0 | 4.0 | 99 | 19.1 |
12/20(24) kV
Nominal Cross Section Area | Nominal Conductor Diameter | Nominal Insulation Thickness | Nominal Screen Cross Section Area |
Nominal Core Sheath Thickness | Nominal Core Diameter | Nominal Bedding Thickness | Nominal Steel Wire Diameter | Serving Thickness |
Overall Diameter |
Weight |
---|---|---|---|---|---|---|---|---|---|---|
mm² | mm | mm | mm² | mm | mm | mm | mm | mm | mm | kg/m |
35 | 7.0 | 5.5 | 16 | 2.5 | 28 | 2 | 3.15 | 3.5 | 78 | 8.8 |
50 | 8.2 | 5.5 | 16 | 2.5 | 30 | 2 | 3.15 | 3.5 | 83 | 9.3 |
70 | 9.9 | 5.5 | 16 | 2.5 | 31 | 2 | 4.0 | 3.5 | 87 | 11.4 |
95 | 11.5 | 5.5 | 16 | 2.5 | 33 | 2 | 4.0 | 3.5 | 89 | 12.7 |
120 | 13.0 | 5.5 | 16 | 2.5 | 34 | 2 | 4.0 | 4.0 | 94 | 14.1 |
150 | 14.5 | 5.5 | 25 | 2.5 | 36 | 2 | 4.0 | 4.0 | 97 | 15.3 |
185 | 16.1 | 5.5 | 25 | 2.5 | 37 | 2 | 5.0 | 4.0 | 102 | 18.6 |
240 | 18.6 | 5.5 | 25 | 2.5 | 40 | 2 | 5.0 | 4.0 | 108 | 21.1 |
18/30(36) kV
Nominal Cross Section Area | Nominal Conductor Diameter | Nominal Insulation Thickness | Nominal Screen Cross Section Area |
Nominal Core Sheath Thickness | Nominal Core Diameter | Nominal Bedding Thickness | Nominal Steel Wire Diameter | Serving Thickness |
Overall Diameter |
Weight |
---|---|---|---|---|---|---|---|---|---|---|
mm² | mm | mm | mm² | mm | mm | mm | mm | mm | mm | kg/m |
50 | 8.2 | 8.0 | 16 | 2.5 | 35 | 2 | 3.15 | 3.5 | 93 | 11.1 |
70 | 9.9 | 8.0 | 16 | 2.5 | 36 | 2 | 4.0 | 4.0 | 99 | 12.8 |
95 | 11.5 | 8.0 | 16 | 2.5 | 38 | 2 | 4.0 | 4.0 | 102 | 14.9 |
120 | 13.0 | 8.0 | 16 | 2.5 | 39 | 2 | 4.0 | 4.0 | 105 | 16.2 |
150 | 14.5 | 8.0 | 25 | 2.5 | 41 | 2 | 4.0 | 4.0 | 108 | 17.6 |
185 | 16.1 | 8.0 | 25 | 2.5 | 42 | 2 | 5.0 | 4.0 | 113 | 21.0 |
240 | 18.6 | 8.0 | 25 | 2.5 | 45 | 2 | 5.0 | 4.0 | 119 | 23.4 |