Airport Cable | |||
400Hz Airport Cables 7-core With Aluminium Wire Armour
Applications
Airprot cables are designed for 400 Hz systems for power supply of aircraft, computer systems and radar
stations, suitable for laying in earth, in water, outdoors, indoors and in cable ducts.
Standards
BS 6724
BS 5467
Construction
Conductor: Stranded bare copper conductor, Class 2.
Insulation: XLPE.
Inner Sheath: LSZH. PVC can be offered upon request.
Armour: Aluminium wire armour.
Outer Sheath: LSZH. PVC can be offered upon request.
Technical Data
Rated Voltage Uo/U (Um) ;600/1000V
Operating Temperatures -40℃~+90℃
Minimum Bending Radius :static: 9×OD; dynamic: 12×OD
Halogen Free :Yes
No Corrosive & Toxic Gases :Yes
Low Smoke :Yes
Dimensions and Weight
Construction | Nominal Diameter of Single Core | Nominal Diameter Under Armour | Nominal Diameter Over Armour | Nominal Overall Diameter | Nominal Weight |
---|---|---|---|---|---|
No. ×mm² | mm | mm | mm | mm | kg/km |
7×35 | 8.6 | 30.0 | 32.4 | 36.6 | 3355 |