Airport Cable  

 2491X to BS 6004 Cables

450/750V PVC Insulated, PVC Sheathed Speaker Cables (4 core)

FGD200 07VV-F (CU/PVC/PVC 450/750V Class 5)

FGD200 07VV-F (CU/PVC/PVC 450/750V Class 5)

APPLICATION

Airprot cables are multicore stranded flexible cables sheathed with thermoplastic PVC compound. The cables can

be offered with the ability to restrict the propagation of the flame in the event of a fire. This is especially

important to slow down the spreading of the fire as the cables may pass from one area to another within a

building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts,

escalators, and high-rise buildings.

STANDARDS

Basic design to BS 6004, BS6500

FIRE PERFORMANCE

FlameRetardance (SingleVerticalWireTest)** EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced FirePropagation(Vertically-mountedbundledwires &cabletest)** EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note:
Asterisk * denotes superseded standard

Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC

compound and the cable design.

VOLTAGE RATING

450/750V

CABLE CONSTRUCTION

Conductor: Plain annealed copper wire, stranded according to BS 6360 Class 5

Insulation: PVC insulation type TI1 to BS 7655

Filler, binder (if any): PP, PET

Outer Sheath: PVC sheath type T6 to BS 7655 COLOUR CODE

Insulation Colour as per BS7671

  withearth conductor withoutearth conductor
2Cores - Brown,Blue
3Cores Yellow/Green,Brown,Blue Brown,Gray,Black
4Cores Yellow/Green,Brown,Gray,Black Brown,Gray,Black,Blue
5Cores Yellow/Green,Brown,Gray,Black,Blue Brown,Gray,Black,Blue,Black
above 5 Cores Yellow/Green,BlackNumbers Black Numbers

Outer sheath: Black or as order

Physical AND THERMAL PROPERTIES

Operating temperature: -15º C to +70º C

Short circuit temperature: +160º C

Minimum bending radius: 4x Overall Diameter

Insulation resistance: 20 MΩxkm

CONSTRUCTION PARAMETERS

Conductor fGD20007VV-f
No.of
CoreXCross
Section
No./
Nominal
Diameterof
Strands
Conductor
Diameter
Nominal
Insulation Thickness
Nominal
Sheath Thickness
Nominal
Overall Diameter
Max.DC resistance ofconductor @20°C Approx. Weight
Noxmm2 No./mm mm mm mm mm Ω/km kg/km
4x1.5 30/0.25 1.6 0.7 1.1 9.5 12.1 152

Electrical PROPERTIES

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

Conductor
cross- sectional area
Reference Method4
(enclosed inconduit in thermally
insulatin
gwalletc)

Reference

Method3 (enclosed inconduit ona wallorin

trunkingetc)

Reference
Method1
(clipped direct)

Reference
Method11
(onaperforated cabletray,
horizontalorvertical)

Reference
Method 12
(freeair)

Horizontalflat spaced

Verticalflat spaced

    Trefoil
2cables, single- phase a.
c.ord.c.
3 or 4cables, 3-phasea
.c.
2cables, single- phase
a.c.ord.c
3 or 4cables, 3-phasea.c. 2cables, single- phase
a.c.or
d.c. flat
andtouching
3 or 4cables, 3-phase
a.c. flat
and
touching or trefoil
2cables,
single-
phase
a.c.or
d.c.o
rflat and touching
3 or 4cables, 3-phase
a.c. flat
and
touching or trefoil

2cables, single- phase
a.c.ord.c.
or 3cables
three phase

2cables, single- phase
a.c.ord.c.
or 3
cables three phase

3cables,
trefoil 3-phasea.c.
  1   2   3   4   5   6   7   8   9   10   11   12
mm2 A A A A A A A A A A A
1.5 18 17 22 19 25 23 - - - - -
Voltage Drop (Per Amp Per Meter)
Nominal
CrossSection Area
2cables d.c. 2cables,
single-phasea.c.
3or 4cables,
3-phase a.c.
Ref.Methods3
and 4 enclosedinconduitetc,inoron a wall)
Ref.Methods1
and11(clippeddirector ontraystouching)
Ref.Methods3
and 4 (enclose
dinconduitetc
,inoron a wall)
Ref.Methods1, Ref.
Methods
1and11
11 and12 (intrefoil) (Flat and
touching)
1 2 3 4 5 6 7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.5 31 31 27 27 27 27