Airport Cable  
 

 CPMS (Car Park Management System)

Talk-back Cable FFX200 05mROZ1-R/F 2G1.0

FFX200 05mROZ1-R 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 2)

FFX200 05mROZ1-F 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 5)

FFX200 05mROZ1-F 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 5)

Applications

Airprot cables are single pair stranded flexible cables sheathed with thermoplastic LSZH compound.Airprot cables

have the ability to restrict the propagation of the flame in the event of a fire.Airprot cable is especially important

to slow down the spreading of the fire as the cables may pass from one area to another within a building.

Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators,

and high-rise buildings.

Standards

Basic design :BS 7629-1

Halogen Free :IEC 60754-1

No corrosive gas emission :IEC 60754-2

Minimum Smoke Emission :IEC 61034-1/2

Reduced Fire Propagation :IEC 60332-3C / NF C 32070-2.2 (C1)

Flame Retardance :IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance :IEC 60331 / NF C 32070-2.3(CR1)

VOLTAGE RATING

300/500V

Construction

Conductors: Plain annealed copper wire, stranded according to EN 60228 class 2 or class 5.

Insulation: Mica glass tape covered by extruded cross-linked XLPE compound.

Cable elements: Insulated cores are twisted to form pairs.

Cabling: Pairs are cabled together.

Overall screen: Aluminum/polyester tape with copper drain wire.

Outer sheath: Thermoplastic LSZH compound.

COLOUR CODE

Insulation Colour: According to IEC 60189-2 (other colour code on request).

Sheath Colour: Colour red (other colours on request).

Electrical PROPERTIES

Dielectric test: 2000 V r.m.s. x 5’ (core/core)

Insulation resistance :1000 MΩ x km (at 20°C)

Short circuit temperature :250°C

Physical AND THERMAL PROPERTIES

Temperature range during operation (fixed state): -30°C – +90°C

Temperature range during installation (mobile state): -20°C – +50°C

Minimum bending radius: 8 × Overall Diameter

CONSTRUCTION PARAMETERS

FFX200 05mROZ1-R 2G1.0

FFX200 05mROZ1-F 2G1.0

No.of core Nominal Cross
Sectional Area
Number &
Nominal Diameter of Strands
Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diameter Approx. Weight
  mm2 No/mm mm mm mm kg/km
2 1.0 7/0.44 0.6 0.9 7.2 64
2 1.0 32/0.2 0.6 0.9 7.2 64