Control Cables

VDE Standard Control Cable

PUR-CY Control Cables

Application:

The specific construction makes this cable type ideal for use in all types of computer systems, office machinery,

signal and control units. This cable type is noted for its excellent mechanical performance in humid and wet

conditions. External high frequency interference is screened out by the tinned copper braiding. These cables are

extremely tear and abrasive resistant. The oil resistance is very good, and also the chemical resistance against

acids, lyes and hydraulic liquids. The cables have good resistance against oils and fats, atmospheric influences,

UV-radiations, oxygene and ozone, microbes and rotting, sea and waste water, vibrations, non-alcoholic fuels

and kerosene.

Conductor

Material: stranded bare copper

Insulation Material: PVC

Core identification:Colours according to DIN47100

Laying UP: multiple cores twisted in layers

Wrapping: fleece wrapping on total (optional).

Screen: tinned copper braid with tinned copper stranded draining wire (only if requested).

Sheath:PUR, grey or other colour.

Minimum bending radius: flexing: 15 x cable diameter static: 6 x cable diameter

Temperature range:Static: -30°C up to + 80°C

Working voltage: peak: (not for purposes of power/high voltage current) 250V

Conductor stranding: strands, fine wire

Colour code: DIN 47100, without colour repetition

In accordance with VDE Regulations: VDE 0814 (DIN 47414) resp. VDE 0812

0.25 mm2 conductor PUR-CY cable

NO. of Cores Cross Section(mm²) Outer Diameter(mm) Copper Weight(kg/100m) Weight
(kg/100m)
1 0.25 4.9 1.4 2.8
2 0.25 7 3.2 6.3
3 0.25 7.6 3.84 7.4
4 0.25 8.3 4.32 8.7
5 0.25 9.3 5.15 10.6
6 0.25 10.1 7.18 13.4
8 0.25 11.4 7.44 15.1
10 0.25 12.5 9 18.8
14 0.25 13.7 11.12 21.7

0.5 mm² conductor PUR-CY cable

NO. of Cores Cross Section(mm²) Outer Diameter(mm) Copper Weight(kg/100m) Weight
(kg/100m)
1 0.5 6.5 2.2 4.9
2 0.5 9.5 5 10.2
3 0.5 10.4 7.18 13.4
4 0.5 11.5 7.44 15.2
5 0.5 11.8 8.45 16.5
6 0.5 12.9 9.96 19.7
8 0.5 15.9 14.43 28.9
10 0.5 17.7 17.6 34.9
14 0.5 18.3 21.54 40.4

0.75 mm² conductor PUR-CY cable

NO. of Cores Cross Section(mm²) Outer Diameter(mm) Copper Weight(kg/100m) Weight
(kg/100m)
1 0.75 7.1 3.4 6.4
2 0.75 9.8 6 11.8
3 0.75 11.1 8.57 15.3
4 0.75 11.6 9.36 17.8
5 0.75 12.8 11.3 20.3
6 0.75 13.7 13.04 23.5
8 0.75 16.7 19.22 34.7
10 0.75 19.3 25.8 46.8
14 0.75 20.3 31.66 54.7

1.0 mm² conductor PUR-CY cable

NO. of Cores

Cross Section(mm²)

Outer Diameter(mm)

Copper Weight(kg/100m)

Weight
(kg/100m)

1 1.0 7.5 4.2 7.4
2 1.0 10.6 7.3 12.8
3 1.0 11.4 9.36 16.7
4 1.0 12.3 11.78 20.9
5 1.0 13.7 13.9 24.1

>>Return