SY PVC /PVC/GSWB/PVC Control Cable
Application:
For use as a measuring, control and signal cable for the machine tool industry, plant construction, heating and
air conditioning, and as a flexible cable between fixed and mobile equipment. The cable is well protected against
mechanical damage by the narrow weave steel-wire braid.
• Note: should not be used in any installations where the cable is subjected to repetitive flexing.
Standards: Generally BS6500 VDE0250
Conductor: Class 5 annealed copper conductors to BS6360 / VDE0295
Insulation: PVC
Bedding: PVC
Braiding: Galvanized Steel Wire Braid (GSWB)
Sheath: PVC (Type TM2 to BS7655)
Voltage Rating: 300/500V
Tempe rature rating:Flexing -15 to +70°C,Static -35 to +70°C
Minimum bending radius: 6 x overall diameter
Core identification: Black with White numbers. (3 core and above to include Green/Yellow)
Coloured cores available on request
Current Carrying Capacity (amperes)
Nominal Cross Sectional Area | Single Phase AC or DC | Three Phase AC |
---|---|---|
mm² | Amps | Amps |
0.5 | 3 | 3 |
0.8 | 6 | 6 |
1.0 | 10 | 10 |
1.5 | 16 | 16 |
2.5 | 25 | 20 |
4.0 | 32 | 25 |
6.0 | 51 | 43 |
10.0 | 70 | 60 |
16.0 | 94 | 80 |
16.0 | 94 | 80 |
The above ratings are based on cable in Free air, in an ambient air temperature of 30°C.
For ambient air temperatures other than 30°C the following rating factors should be applied:
Ratings for cables up to and including 4mm2 are based on 60°C conductor operating temperature with 6mm2
and above based on 70°C operating temperature.
Correction Factors
Cables Up To and Including 4mm2 . Assuming 60°C Conductor Temperature
Ambient Temperature | 35°C | 40°C | 45°C | 50°C | 55°C |
---|---|---|---|---|---|
Correction Factor | 0.91 | 0.82 | 0.71 | 0.58 | 0.41 |
Cables 6mm2 and above . Assuming 70°C Conductor Temperature
Ambient Temperature | 35°C | 40°C | 45°C | 50°C | 55°C | 60°C |
---|---|---|---|---|---|---|
Correction Factor | 0.91 | 0.82 | 0.71 | 0.58 | 0.41 | 0.50 |
3 Core SY control cable
No. of Cores | Nominal Cross Sectional Area | Nominal No. and Size of Wires | Nominal Overall Diameter | Nominal Weight |
---|---|---|---|---|
mm² | #/mm | mm | kg/Km | |
3 | 1.0 | 32/0.20 | 9.0 | 142 |
3 | 1.5 | 30/0.25 | 10.2 | 186 |
3 | 2.5 | 50/0.25 | 11.9 | 246 |
3 | 4.0 | 56/0.30 | 15.1 | 330 |
3 | 6.0 | 84/0.30 | 16.2 | 407 |
3 | 10.0 | 80/0.40 | 20.1 | 621 |
3 | 16.0 | 126/0.40 | 23.8 | 857 |
4 Core SY control cable
No. of Cores | Nominal Cross Sectional Area | Nominal No. and Size of Wires | Nominal Overall Diameter | Nominal Weight |
---|---|---|---|---|
mm² | #/mm | mm | kg/Km | |
4 | 1.0 | 32/0.20 | 9.8 | 165 |
4 | 1.5 | 30/0.25 | 10.9 | 212 |
4 | 2.5 | 50/0.25 | 13.4 | 315 |
4 | 4.0 | 56/0.30 | 16.4 | 457 |
4 | 6.0 | 84/0.30 | 19.5 | 687 |
4 | 10.0 | 80/0.40 | 24.2 | 1009 |
4 | 16.0 | 126/0.40 | 27.1 | 1384 |
5 Core SY control cable
No. of Cores | Nominal Cross Sectional Area | Nominal No. and Size of Wires | Nominal Overall Diameter | Nominal Weight |
---|---|---|---|---|
mm² | #/mm | mm | kg/Km | |
5 | 1.0 | 32/0.20 | 10.5 | 197 |
5 | 1.5 | 30/0.25 | 11.7 | 241 |
5 | 2.5 | 50/0.25 | 14.5 | 365 |
5 | 4.0 | 56/0.30 | 17.7 | 545 |
5 | 6.0 | 84/0.30 | 21.1 | 798 |
5 | 10.0 | 80/0.40 | 26.2 | 1197 |
5 | 16.0 | 126/0.40 | 30.6 | 1740 |
7 Core SY control cable
No. of Cores | Nominal Cross Sectional Area | Nominal No. and Size of Wires | Nominal Overall Diameter | Nominal Weight |
---|---|---|---|---|
mm² | #/mm | mm | kg/Km | |
7 | 1.0 | 32/0.20 | 11.2 | 231 |
7 | 1.5 | 30/0.25 | 13.1 | 310 |
7 | 2.5 | 50/0.25 | 15.5 | 458 |