Industrial Cables | |||
H03VV-F | H05VV-F | H07RN-F | more |
Australian Standard (Medium Voltage)
19/33kV Three Core Individual Screened & PVC Sheathed (Al Conductor)
Application
19/33kV Three Core Individual Screened & PVC Sheathed (Al Conductor) cables are designed to be used for the
supply of electrical energy in fixed applications up to the rated voltages at a nominal power frequency between
49Hz and 61Hz., 19/33kV Three Core Individual Screened & PVC Sheathed (Al Conductor) cables are suitable for
use in distribution installation, electrical power station , they are applied for installation, outdoors, underground
where subject to mechanical damage.
Standard
AS/NZS 1429.1
Cable Construction
CONDUCTOR: Plain circular compacted aluminium to AS/NZS1125 Maximum Continuous
Operating Temperature: 90°C
CONDUCTOR SCREEN: Extruded semi-conducting compound, bonded to the insulation and applied in the same
operation as the insulation
INSULATION: Cross Linked Polyethylene (XLPE) – standard Ethylene Propylene Rubber (EPR) – alternative
INSULATION SCREEN: Extruded semi-conducting compound
METALLIC SCREEN: Plain annealed copper wire: 3kA for nominal 1 second(LIGHT DUTY) Plain annealed copper
wire: 10kA for nominal 1 second(HEAVY DUTY)
SHEATH: Black 5V-90 polyvinyl chloride (PVC) – standard
Orange 5V-90 PVC inner plus black high density polyethylene (HDPE) outer – alternative Low smoke zero
halogen (LSOH) – alternative
Technical Characteristics
LIGHT DUTY
Nominal conductor area | Maximum Conductor DC resistance at 20°C | Cond. AC resistance at 50Hz and 90°C | Inductive reactance at 50Hz | Insulation resistance at 20°C | Conductor to screen capacitance | Maximum diaelectric stress | Current Ratings | ||
---|---|---|---|---|---|---|---|---|---|
Unenclosed In Air | Unenclosed In Air | Unenclosed In Air | |||||||
mm | Ohm/km | Ohm/km | Ohm/km | MegOhm.km | µF x km | kV x mm | A | A | A |
50 | 0.641 | 0.821 | 0.147 | 18000 | 0.134 | 4.04 | 164 | 155 | 134 |
70 | 0.443 | 0.568 | 0.136 | 16000 | 0.148 | 3.81 | 203 | 189 | 163 |
95 | 0.32 | 0.41 | 0.129 | 15000 | 0.164 | 3.62 | 246 | 226 | 198 |
120 | 0.253 | 0.325 | 0.124 | 14000 | 0.176 | 3.5 | 283 | 257 | 226 |
150 | 0.206 | 0.264 | 0.12 | 13000 | 0.189 | 3.4 | 319 | 288 | 252 |
Cable Parameter
LIGHT DUTY
Sectional Area of Conductor | Nom. Conductor Diameter | Nom. Insulation Thickness | Nom. Diamete Over insulation | Screen Area on Each core | No. and Diamter of Screened Wires | Nom. Diamete Over Screened Wires | Nom. Overall Diameter | Approx. mass |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm2 | no x mm | mm | mm | kg/100m |
50 | 8.1 | 8 | 25.6 | 9.6 | 17 x 0.85 | 26.1 | 66.7 | 322 |
70 | 9.6 | 8 | 27.2 | 10.2 | 18 x 0.85 | 27.6 | 70.4 | 367 |
95 | 11.4 | 8 | 28.9 | 10.8 | 19 x 0.85 | 29.3 | 74.2 | 418 |
120 | 12.8 | 8 | 30.3 | 11.3 | 20 x 0.85 | 30.7 | 77.5 | 463 |
150 | 14.2 | 8 | 31.7 | 11.9 | 21 x 0.85 | 32.1 | 80.7 | 510 |
Technical Characteristics
HEAVY DUTY
Nominal conductor area | Maximum Conductor DC resistance at 20°C | Cond. AC resistance at 50Hz and 90°C | Inductive reactance at 50Hz | Insulation resistance at 20°C | Conductor to screen capacitance | Maximum diaelectric stress | Current Ratings | ||
---|---|---|---|---|---|---|---|---|---|
Unenclosed In Air | Unenclosed In Air | Unenclosed In Air | |||||||
mm2 | Ohm/km | Ohm/km | Ohm/km | MegOhm.km | µF x km | kV x mm | A | A | A |
50 | 0.641 | 0.821 | 0.147 | 18000 | 0.134 | 4.04 | 164 | 155 | 134 |
70 | 0.443 | 0.568 | 0.136 | 16000 | 0.148 | 3.81 | 203 | 189 | 163 |
95 | 0.32 | 0.41 | 0.129 | 15000 | 0.164 | 3.62 | 246 | 226 | 198 |
120 | 0.253 | 0.325 | 0.124 | 14000 | 0.176 | 3.5 | 283 | 257 | 226 |
150 | 0.206 | 0.264 | 0.12 | 13000 | 0.189 | 3.4 | 319 | 288 | 252 |
185 | 0.164 | 0.211 | 0.117 | 12000 | 0.202 | 3.31 | |||
240 | 0.125 | 0.161 | 0.112 | 11000 | 0.222 | 3.2 | |||
300 | 0.1 | 0.13 | 0.108 | 10000 | 0.242 | 3.11 | |||
400 | 0.0778 | 0.102 | 0.103 | 9100 | 0.267 | 3.02 | |||
500 | 0.0617 | 0.0815 | 0.099 | 8100 | 0.297 | 2.93 |
Cable Parameter
HEAVY DUTY
Sectional Area of Conductor | Nom. Conductor Diameter | Nom. Insulation Thickness | Nom. Diamete Over insulation | Screen Area on Each core | No. and Diamter of Screened Wires | Nom. Diamete Over Screened Wires | Nom. Overall Diameter | Approx. mass |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm2 | no x mm | mm | mm | kg/100m |
50 | 8.1 | 8 | 25.6 | 10.8 | 19 x 0.85 | 28.9 | 69.5 | 355 |
70 | 9.6 | 8 | 27.2 | 15.3 | 27 x 0.85 | 30.5 | 73.1 | 415 |
95 | 11.4 | 8 | 28.9 | 20.4 | 36 x 0.85 | 32.2 | 77 | 480 |
120 | 12.8 | 8 | 30.3 | 22.7 | 40 x 0.85 | 33.6 | 80.2 | 525 |
150 | 14.2 | 8 | 31.7 | 22.7 | 40 x 0.85 | 35.2 | 83.9 | 580 |
185 | 15.7 | 8 | 33.2 | 22.7 | 40 x 0.85 | 36.7 | 87.3 | 635 |
240 | 18 | 8 | 35.5 | 22.7 | 40 x 0.85 | 39 | 92.9 | 730 |
300 | 20.1 | 8 | 37.8 | 22.7 | 40 x 0.85 | 41.3 | 98.1 | 820 |
400 | 23 | 8 | 40.7 | 22.7 | 40 x 0.85 | 44.2 | 104.8 | 955 |
500 | 26.5 | 8 | 44.2 | 22.7 | 40 x 0.85 | 47.7 | 112.9 | 1120 |