Industrial Cables | |||
H03VV-F | H05VV-F | H07RN-F | more |
Industrial Cables
H05G-K/H07G-K
Application and Description
H05G-K/H07G-K cables are recommended for the internal wiring of switchboards and distributor boards as well
as in operating parts in or on lights. The higher temperature range allows for connections to heaters with an
alternating nominal voltage of 1000V. or direct nominal voltage of 750V.H05G-K/H07G-K cables are all allowed
for laying in tubes in and under plaster.
Standard and Approval
HD 22.7 S2, VDE-0282 Part-7
Cable Construction
Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5
Rubber compound type EI3 (EVA) to DIN VDE 0282 part 7 insulation
Cores to VDE-0293 colors
Technical Characteristics
Working voltage: 300/500v (H05G-K), 450/750v (H07G-K)
Test voltage: 2000volts (H05G-K), 2500 volts (H07G-K)
Flexing bending radius: 7 x Ø
Static bending radius: 7 x Ø
Flexing temperature: -25º C to +110º C
Static temperature: -40º C to +110º C
Short circuit Temperature: +160º C
Flame retardant: IEC 60332.1
Insulation resistance: 10 MΩ x km
Cable Parameter
AWG | No. of Cores x Nominal Cross Sectional Area #x mm² | Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm |
Nominal Copper Weight kg/Km | Nominal Weight kg/Km |
---|---|---|---|---|---|
H05G-K | |||||
20(16/32) | 1 x 0.5 | 0.6 | 2.3 | 4.8 | 13 |
18(24/32) | 1 x 0.75 | 0.6 | 2.6 | 7.2 | 16 |
17(32/32) | 1 x 1 | 0.6 | 2.8 | 9.6 | 22 |
H07G-K | |||||
16(30/30) | 1 x 1.5 | 0.8 | 3.4 | 14.4 | 24 |
14(50/30) | 1 x 2.5 | 0.9 | 4.1 | 24 | 42 |
12(56/28) | 1 x 4 | 1.0 | 5.1 | 38 | 61 |
10(84/28) | 1 x 6 | 1.0 | 5.5 | 58 | 78 |
8(80/26) | 1 x 10 | 1.2 | 6.8 | 96 | 130 |
6(128/26) | 1 x 16 | 1.2 | 8.4 | 154 | 212 |
4(200/26) | 1 x 25 | 1.4 | 9.9 | 240 | 323 |
2(280/26) | 1 x 35 | 1.4 | 11.4 | 336 | 422 |
1(400/26) | 1 x 50 | 1.6 | 13.2 | 480 | 527 |
2/0(356/24) | 1 x 70 | 1.6 | 15.4 | 672 | 726 |
3/0(485/24) | 1 x 95 | 1.8 | 17.2 | 912 | 937 |
4/0(614/24) | 1 x 120 | 1.8 | 19.7 | 1152 | 1192 |