Industrial Cables  
H03VV-F H05VV-F H07RN-F more

Industrial Cables

H07V-K

Application and Description

H07V-K cables are not suitable to be installed for laying in tubes, under and surface mounting of plaster and

also in closed installation conduits. These are not allowed to install for direct laying on cable trays, channel or

tanks. These types are permitted for the inner wiring of equipment, distributor and switchboards and also for

protective laying to the lightings with a nominal voltage up to 1000 V alternating current or up to 750 V direct

current against earth.

Standard and Approval

HD 21.3 S3, VDE-0281 Part-3

Cable Construction

H07V-KH07V-K

Fine bare copper strands

Strands to VDE-0295 Class-5, IEC 60228 Class-5

Special PVC TI1 core insulation

Cores to VDE-0293 colors on chart

Technical Characteristics

Working voltage: 450/750V

Test voltage: 2500 volts

Flexing bending radius: 12.5 x Ø

Static bending radius: 12.5 x Ø

Flexing temperature: -5º C to +70º C

Static temperature: -30º C to +80º C

Short circuit temperature: +160º C

Flame retardant: IEC 60332.1

Insulation resistance: 10 MΩ x km

Cable Parameter

AWG No. of Cores x Nominal Cross Sectional Area # x mm² Nominal Thickness of Insulation mm Nominal Overall Diameter
mm
Nominal Copper Weight kg/Km Nominal Weight kg/Km
16(30/30) 1 x 1.5 0,7 3.1 14.4 20
14(50/30) 1 x 2.5 0,8 3.6 24.0 31
12(56/28) 1 x 4 0,8 4.3 38.0 48
10(84/28) 1 x 6 0,8 4.9 58.0 69
8(80/26) 1 x 10 1,0 6.4 96.0 121
6(128/26) 1 x 16 1,0 8.1 154.0 211
4 (200/26) 1 x 25 1,2 9.8 240 303
2 (280/26) 1 x 35 1,2 11.1 336 417
1 (400/26) 1 x 50 1,4 13.1 480 539
2/0 (356/24) 1 x 70 1,4 15.5 672 730
3/0 (485/24) 1 x 95 1,6 17.2 912 900
4/0 (614/24) 1 x 120 1,6 19.7 1152 1135
300 MCM (765/24) 1 x 150 1,8 21.3 1440 1410
350 MCM (944/24) 1 x 185 2,0 23.4 1776 1845
500MCM(1225/24) 1 x 240 2,2 27.1 2304 2270