Industrial Cables |
American | French | German | Harmonized | Italian | JIS | Spanish |
Industrial Cables-British Standard
6381Y to BS 6004 & IEC60502
Application and Description
6381Y to BS 6004 & IEC60502 cables are designed for DC power supplies on Telecom equipment and power
applications where flexibility is required.
Cable Construction
-
Bare copper conductor
Stranding to BS6360 CL-5 or IEC60228 CL-5
PVC insulation Type TI1 to BS7655
PVC sheath Type TM1 to BS7655
oxygen index> 30%
Meets requirements for flammability as required by BT specification M231
Sheath/Core Identification
-
Blue (Blue), Grey (Grey), Green/Yellow (Green/Yellow), Brown (Brown), Special colours to order
Technical Characteristics
-
Working voltage: 1.0mm² to 35mm² - 450/750V
50mm² and above - 600/1000V
- Operating temperature: -15º C to +70º C
Insulation resistance: 10 MΩxkm
Flame retardant: IEC 60332.1, BS4066 Part 1
Cable Parameter
AWG (No of Strands/ Strand Diameter) |
No. of Cores x Nominal Cross Sectional Area #xmm² |
Nominal Thickness of Insulation mm |
Nominal Thickness of Sheath mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
---|---|---|---|---|---|
16(30/30) | 1x1.5 | 0.9 | 0.8 | 4.9 | 36 |
14(50/30) | 1x2.5 | 0.9 | 0.8 | 5.4 | 52 |
12(56/28) | 1x4 | 1 | 0.9 | 6.3 | 76 |
10(84/28) | 1x6 | 1.1 | 0.9 | 7.6 | 100 |
8(80/26) | 1x10 | 1.2 | 1 | 8.6 | 160 |
6(128/26) | 1x16 | 1.2 | 1 | 9.8 | 230 |
4(200/26) | 1x25 | 1.4 | 1.1 | 11.5 | 340 |
2(280/26) | 1x35 | 1.4 | 1.1 | 12.5 | 440 |
1(400/26) | 1x50 | 1.4 | 1.4 | 15.1 | 541 |
2/0(356/24) | 1x70 | 1.4 | 1.4 | 17.0 | 749 |
3/0(485/24) | 1x95 | 1.6 | 1.5 | 19.1 | 1000 |
4/0(614/24) | 1x120 | 1.6 | 1.8 | 21.6 | 1241 |
300MCM (765/24) | 1x150 | 1.8 | 1.8 | 23.4 | 1523 |
350MCM (944/24) | 1x185 | 2 | 1.8 | 25.5 | 1942 |
500MCM(1225/24) | 1x240 | 2.2 | 1.8 | 28.5 | 2514 |
-(1525/24) | 1x300 | 2.4 | 2 | 31.2 | 3125 |
-(2013/24) | 1x400 | 2.6 | 2.1 | 35.3 | 3967 |
-(1769/23) | 1x500 | 2.8 | 2.2 | 38.8 | 5063 |
-(2257/23) | 1x630 | 2.8 | 2.4 | 43.8 | 6491 |