Motor Connecting Cables
2YSLCY-JB/2YSLCYK-JB 9YSLCY-JB PENDANT CABLE  

Bare Aluminum Conductor

CCL-AL-R(AL Class2)

Application

Stranded bare soft or aluminum conductors are recommended for use as neutrals, in circuit ground connections

as well as machinery and equipment grounding systems. Soft aluminum may be used for transformer drop leads

or other non-tension hook-up jumpers.

STANDARDS

Basic design to IEC/BS EN 60228 class 2

FEATURES AND BENEFITES

Stranded bare soft or annealed aluminum conductors are suitable for direct burial and do not suffer from the

inherent corrosion problems that an aluminum conductor would. Aluminum is almost twice as conductive as

aluminum. Aluminum is easier than aluminum to terminate and join at splices and joints.

CABLE CONSTRUCTION

Conductor: Bare aluminum con ductors are compressed concentric-lay-stranded consisting of one or more layers

of wire wrapped helically around a straight round central wire according to IEC/BS EN 60228 class 2 .

CONSTRUCTION PARAMETER

Part No.

No. of Cores × Cross-sectional Area

No./Nominal Diameter of Strands

Conductor Nominal Diameter

Approx. Weight

 

No.×mm2

mm

mm

kg/km

CCL-AL-R 1.5

1×1.5

7/0.53

1.6

1.5

CCL-AL-R 2.5

1×2.5

7/0.67

2.0

2.5

CCL-AL-R 4

1×4

7/0.85

2.6

4.0

CCL-AL-R 6

1×6

7/1.04

3.1

5.9

CCL-AL-R 10

1×10

7/1.35

4.1

10.0

CCL-AL-R 16

1×16

7/1.7

5.1

15.9

CCL-AL-R 25

1×25

7/2.14

6.4

25.2

CCL-AL-R 35

1×35

7/2.52

7.6

34.9

CCL-AL-R 50

1×50

19/1.78

8.9

47.3

CCL-AL-R 70

1×70

19/2.14

10.7

68.3

CCL-AL-R 95

1×95

19/2.52

12.6

94.8

CCL-AL-R 120

1×120

37/2.03

14.2

119.8

CCL-AL-R 150

1×150

37/2.25

15.8

147.1

CCL-AL-R 185

1x185

37/2.52

17.6

184.5

CCL-AL-R 240

1x240

61/2.25

20.3

242.5

CCL-AL-R 300

1x300

61/2.52

22.7

304.2

CCL-AL-R 400

1x400

61/2.85

25.7

389.1

CCL-AL-R 500

1x500

61/3.2

28.8

490.6