Submersible pump cables | |||
PVC 3 Core Flat Cables | PVC 4 Core Flat Cables | PVC 3 Core Round Cables | more |
Submersible pump cables
Rubber 3 Core Flat Cables
Applications:
- For continuous use in deep well to supply power to submersible pumps down to depths of 500 mtrs.
FEATURES:
Meets the requirement of CENELEC HD 22.1.S2, DIN VDE 0282 PART 810, IEC 245, CEI 20-19 & BS 6007, BS
6899.
Cur, tear & abrasion resistant.
Exceptional long term performance.
Excellent resistant to oils, chemicals,
ozone & solvents.
Excellent Impact Resistant.
Excellent Weather Resistant.
Performs & Looks like Vulcanize Rubber.
Construction :
CONDUCTOR | RUBBER INSULATION | RUBBER SHEATH | Conductor Resistance at 20°C (max) ohms/km | CURRENT Rating at 40°C Amps. |
||||
---|---|---|---|---|---|---|---|---|
Nominal Area in |
Nos. & Dia. of wire |
Nominal Thickness |
Nominal Core Dia. |
Nominal Thickness |
Approx. Overall Dimensions |
|||
Sq. mm. | Nos. / mm | mm | mm | mm | Thickness mm |
Width mm |
||
1.50 | 22/0.30 | 0.80 | 3.25 | 1.15 | 6.00 | 12.80 | 12.10 | 14 |
2.50 | 36/0.30 | 0.90 | 3.84 | 1.15 | 6.40 | 14.60 | 7.41 | 18 |
4.00 | 56/0.30 | 1.00 | 4.50 | 1.15 | 7.40 | 16.80 | 4.95 | 26 |
6.00 | 85/0.30 | 1.00 | 5.30 | 1.15 | 7.90 | 18.70 | 3.30 | 31 |
10.00 | 140/0.30 | 1.00 | 6.50 | 1.40 | 9.90 | 23.70 | 1.91 | 42 |
16.00 | 226/0.30 | 1.00 | 8.00 | 1.40 | 11.40 | 28.00 | 1.21 | 57 |
25.00 | 354/0.30 | 1.20 | 10.10 | 2.00 | 14.70 | 35.50 | 0.780 | 72 |
35.00 | 495/0.30 | 1.20 | 11.30 | 2.00 | 16.20 | 39.50 | 0.554 | 90 |
50.00 | 703/0.30 | 1.40 | 13.60 | 2.20 | 18.30 | 45.50 | 0.386 | 115 |
70.00 | 440/0.45 | 1.40 | 15.30 | 2.20 | 20.00 | 51.00 | 0.272 | 143 |
95.00 | 475/0.50 | 1.60 | 18.00 | 2.40 | 23.50 | 60.00 | 0.206 | 165 |