Special Cables
Trailing cables Cables for renewable energy Single Conductor Airport 400Hz Truck cables more

Flexible, Double insulated single conductor

Application

PVC single-conductor cable suitable for medium mechanical stresses with free movement without tensile stress

or forced movements in dry, moist and wet rooms, and in open air (fixed installation).Must not be installed

directly in the ground or water.This two-approvals single-conductor cable is preferred for use in export-oriented

mechanical engineering, in machine tools, production lines and systems engineering.

Cable Construction

Bare copper conductor, fine wire stranded

1st Insulation: special PVC, color black

2nd Insulation: special PVC

Jacket color black

Temperature range:

flexing -5°C to +90°C; fixed installation -40°C to +90°C

Nominal voltage:

acc. to VDE U0/U 600/1000 V; acc. to UL 1000 V

A.C. test voltage, 50 Hz:

4000 V

Minimum bending radius:

for flexible installation; approx. 7,5x cable Ø; for fixed installation; approx. 3x cable Ø

Properties

PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/ EN 50265-2-1/ IEC 60332-1

(equivalent DIN VDE 0472 part 804 test method B)

Conductors x cross-sec. mm² Outer
Diameter
Copper weight
kg/km
Weight
ca. kg/km
AWG
1x1.5 4.5 14.4 30.0 16
1x2.5 5.0 24.0 49.0 14
1x4 6.1 38.4 75.0 12
1x6 7.2 57.6 118.0 10
1x10 9.0 96.0 180.0 8
1x16 10.2 154.0 250.0 6
1x25 11.6 240.0 370.0 4
1x35 13.0 336.0 490.0 2
1x50 16.0 480.0 665.0 1
1x70 17.1 672.0 910.0 2/0
1x95 19.5 912.0 1195.0 3/0
1x120 22.3 1152.0 1545.0 4/0