APPLICATION :

EN 50288-7 cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petr°Chemistry industry plants, power plants, natural gas and petroluem plants, etc... EN 50288-7 cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, EN 50288-7 cables inhibit the propagation of the flames whereby the development of smoke is extremely low.Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet l°Cations; on racks, trays, in conduits.

STANDARDS :

EN 50288-7 Cables

Basic design to EN 50288-7

FIRE PERFORMANCE:

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% oftensile strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING :

300V

CABLE CONSTRUCTION :

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pair:Two conductors twisted to form a pair

Lay-up: Pairs laid up in layers of optimum pitch

Separator: Polyester tape

Overall Screen: Tinned copper wire braid

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti odent and anti termite properties can be offered as option.

COLOUR CODE :

Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.

Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES :

Temperature Range During Operation (Fixed State): -30°C – +70°C

Temperature Range During Installation (Mobile State): -5°C – +50°C

Minimum Bending Radius: 7.5 X Overall Diameter

Electrical PROPERTIES :

Conductor Area Size mm² 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C)  Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Capacitance unbalance(1 kHz) pF/500 m (Max.) 300
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500

CONSTRUCTION PARAMETERS :

Caledonian Cable Code RE-2X(C)H
No. of Pairs x2xCross Section Copper
Weight
  No.x2xmm2 Kg/km

RE-2X(C)H 1P0.5

1x2x0.50

8.3

RE-2X(C)H 1P0.75

1x2x0.75

8.7

RE-2X(C)H 1P1.0

1x2x1.0

9.4

RE-2X(C)H 1P1.3

1x2x1.3

9.7

Note : Other conductor sizes & core configurations are available upon request.