PE Insulated, PVC Sheathed & Overall Screened Instrumentation Cables (Multipair)
APPLICATION :
EN 50228-7 unarmoured LSZH sheathed cables are generally use for indoor installation and suitable for wet and damp areas. Generally,EN 50228-7 cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, EN 50228-7 LSZH sheath can reduce toxic smoke and fume emission.
STANDARDS:
Basic design to EN 50288-7
FIRE PERFORMANCE:
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
---|---|
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance | ICEA S-73-532** |
Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of
tensite strength/min.60% of elongation.
VOLTAGE RATING:
300V
CABLE CONSTRUCTION:
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: PE compound, EN 50290. 2-23.
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound typeSW2-SW4 as per BS 76552.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE:
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems
PHYSICAL AND THERMAL PROPERTIES:
Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter
ELECTRICAL PROPERTIES:
Conductor Area Size | mm 2 | 0.5 |
0.75 |
1.0 |
1.3 |
1.5 |
|
---|---|---|---|---|---|---|---|
Insulation thickness (nominal) | mm | 0.35 |
0.38 |
0.4 |
0.45 |
0.45 |
|
Conductor resistance (20°C) | Ω/km | 36.7 |
25 |
18.5 |
14.2 |
12.3 |
|
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 |
|||||
Mutual Capacitance (1 kHz) | pF/m(Max.) |
|
|||||
≤ 4 pairs | 90 |
90 |
90 |
102 |
102 |
||
all other pairs | 75 |
75 |
75 |
85 |
85 |
||
Capacitance unbalance(1 kHz) | pF/500 m (Max.) | 500 |
|||||
Inductance | mH/km (Max.) | 1 |
|||||
L / R (ratio) (max.) | μH/Ω | 25 |
25 |
25 |
40 |
40 |
|
Operating voltage Urms | V | 300 |
|||||
Test Voltage | Core to Core | V | 1500 |
||||
Core to Screen | V | 1500 |
CONSTRUCTION PARAMETERS:
Caledonian Cable Code | RE-2Y(St)H | ||
---|---|---|---|
No. of Pairsx2 xCross Section |
Nominal Insulation Thickness | Nominal Outer Sheath Thickness | |
No.x2xmm2 | mm | mm | |
0.5mm2, Multipair |
|||
RE-2Y(St)H 2P0.5 |
2x2x0.5 |
0.35 |
0.9 |
RE-2Y(St)H 4P0.5 |
4x2x0.5 |
0.35 |
0.9 |
RE-2Y(St)H 5P0.5 |
5x2x0.5 |
0.35 |
1.0 |
RE-2Y(St)H 6P0.5 |
6x2x0.5 |
0.35 |
1.0 |
RE-2Y(St)H 8P0.5 |
8x2x0.5 |
0.35 |
1.0 |
RE-2Y(St)H 10P0.5 |
10x2x0.5 |
0.35 |
1.1 |
RE-2Y(St)H 12P0.5 |
12x2x0.5 |
0.35 |
1.1 |
RE-2Y(St)H 16P0.5 |
16x2x0.5 |
0.35 |
1.1 |
RE-2Y(St)H 20P0.5 |
20x2x0.5 |
0.35 |
1.2 |
RE-2Y(St)H 24P0.5 |
24x2x0.5 |
0.35 |
1.2 |
0.75mm2, Multipair |
|||
RE-2Y(St)H 2P0.75 |
2x2x0.75 |
0.38 |
0.9 |
RE-2Y(St)H 4P0.75 |
4x2x0.75 |
0.38 |
1.0 |
RE-2Y(St)H 5P0.75 |
5x2x0.75 |
0.38 |
1.0 |
RE-2Y(St)H 6P0.75 |
6x2x0.75 |
0.38 |
1.0 |
RE-2Y(St)H 8P0.75 |
8x2x0.75 |
0.38 |
1.1 |
RE-2Y(St)H 10P0.75 |
10x2x0.75 |
0.38 |
1.1 |
RE-2Y(St)H 12P0.75 |
12x2x0.75 |
0.38 |
1.1 |
RE-2Y(St)H 16P0.75 |
16x2x0.75 |
0.38 |
1.2 |
RE-2Y(St)H 20P0.75 |
20x2x0.75 |
0.38 |
1.3 |
RE-2Y(St)H 24P0.75 |
24x2x0.75 |
0.38 |
1.3 |
RE-2Y(St)H 2P1.0 |
2x2x1.0 |
0.4 |
0.9 |
RE-2Y(St)H 4P1.0 |
4x2x1.0 |
0.4 |
1.0 |
RE-2Y(St)H 5P1.0 |
5x2x1.0 |
0.4 |
1.0 |
RE-2Y(St)H 6P1.0 |
6x2x1.0 |
0.4 |
1.0 |
RE-2Y(St)H 8P1.0 |
8x2x1.0 |
0.4 |
1.1 |
RE-2Y(St)H 10P1.0 |
10x2x1.0 |
0.4 |
1.1 |
RE-2Y(St)H 12P1.0 |
12x2x1.0 |
0.4 |
1.2 |
RE-2Y(St)H 16P1.0 |
16x2x1.0 |
0.4 |
1.2 |
RE-2Y(St)H 20P1.0 |
20x2x1.0 |
0.4 |
1.3 |
RE-2Y(St)H 24P1.0 |
24x2x1.0 |
0.4 |
1.4 |
1.3mm2, Multipair |
|||
RE-2Y(St)H 2P1.3 |
2x2x1.3 |
0.45 |
1.0 |
RE-2Y(St)H 4P1.3 |
4x2x1.3 |
0.45 |
1.0 |
RE-2Y(St)H 5P1.3 |
5x2x1.3 |
0.45 |
1.1 |
RE-2Y(St)H 6P1.3 |
6x2x1.3 |
0.45 |
1.1 |
RE-2Y(St)H 8P1.3 |
8x2x1.3 |
0.45 |
1.2 |
RE-2Y(St)H 10P1.3 |
10x2x1.3 |
0.45 |
1.2 |
RE-2Y(St)H 12P1.3 |
12x2x1.3 |
0.45 |
1.3 |
RE-2Y(St)H 16P1.3 |
16x2x1.3 |
0.45 |
1.3 |
RE-2Y(St)H 20P1.3 |
20x2x1.3 |
0.45 |
1.4 |
RE-2Y(St)H 24P1.3 |
24x2x1.3 |
0.45 |
1.5 |
1.5mm2, Multipair |
|||
RE-2Y(St)H 2P1.5 |
2x2x1.5 |
0.45 |
1.0 |
RE-2Y(St)H 4P1.5 |
4x2x1.5 |
0.45 |
1.1 |
RE-2Y(St)H 5P1.5 |
5x2x1.5 |
0.45 |
1.1 |
RE-2Y(St)H 6P1.5 |
6x2x1.5 |
0.45 |
1.2 |
RE-2Y(St)H 8P1.5 |
8x2x1.5 |
0.45 |
1.2 |
RE-2Y(St)H 10P1.5 |
10x2x1.5 |
0.45 |
1.3 |
RE-2Y(St)H 12P1.5 |
12x2x1.5 |
0.45 |
1.3 |
RE-2Y(St)H 16P1.5 |
16x2x1.5 |
0.45 |
1.4 |
RE-2Y(St)H 20P1.5 |
20x2x1.5 |
0.45 |
1.5 |
RE-2Y(St)H 24P1.5 |
24x2x1.5 |
0.45 |
1.5 |
Note : Other conductor sizes & core configurations are available upon request.