HOMEPRODUCTSBUS CABLES

 

Bus Cables

E.I.B Cable(European Installation Bus)

 

 

 

E.I.B Cable(European Installation Bus)

Application:

EIB installation consists of sensors and actuators. The E.I.B. concept allows intergration of Building Management Systems (B.M.S.) over one common system. Lighting, blinds, heating and ventilation can be automatically controlled through the E.I.B cable. This dramatically reduces the cabling required in a modern building. To meet European standards this cable is LSHF throughout. They can be installed over, in, or below the plaster, in pipes and pipe ducts, in dry, moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun.

Construction:

Type/Cable Construction

1 Quad

2 Pair

Inner Conductor

Plain copper conductors 0.8mm

Plain copper conductors 0.8mm

Conductor Insulation

Polyethylene

Polyethylene

Conductor Colors

White,yellow,red,black

White,yellow,red,black

Stranding Element

Cores twisted into a quad

Cores twisted into pairs, pairs laid up

Core Wrapping

-

-

Shielding

Aluminium/polyester foil screen

Aluminium/polyester foil screen

drain wire

Solid copper

Stranded tinned copper

Outer Jacket

Low Smoke Halogen Free

Low Smoke Halogen Free

Sheath Colour

Green

Green

Electrical Data:

Test Voltage:4KV

Working Voltage :Max.150V

Conductor resistance :37.0 Ohm/km @ 20°C

Insulation resistance:1000MΩhms*km @ 20°C

Mutual capacitance@800Hz:100nF/km max

Unbalanced capacitance:300pF/100m max

Technical Data:

Weight:

approximately 62.0 kg/km

approximately 57.0 kg/km

Min. Bending Radius (Laying):

10 x OD mm

10 x OD mm

Operating temperature, min

-20°C(fixed)

-5°C (installation)

Operating temperature, max

+70°C(fixed)

+50°C(installation)