450/750V Mica+LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-31 (Single Core)
FFX100 07mZ1-U/R/K (CU/MGT+LSZH 450/750V Class 1/2/5)
APPLICATION:
The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.
STANDARDS:
Basic design adapted from BS EN 50525-3-31
FIRE PERFORMANCE:
Circuit Integrity |
IEC 60331-21; BS 6387; BS 8491 |
---|---|
Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
Halogen free | IEC 60754-1; EN 50267-2-1 |
No Corrosive Gas Emission | IEC60754-2; EN 50267-2-2 |
Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
VOLTAGE RATING:
450/750V
CABLE CONSTRUCTION:
Conductor : Copper conductor according to BS EN 60228 class 1/2/5.
FFX100 07mZ1-U : 1.5-10mm² Class 1 solid copper conductor to BS EN 60228.
FFX100 07mZ1-R : 1.5-630mm² Class 2 stranded copper conductor to BS EN 60228.
FFX100 07mZ1-K : 1.5-240mm² Class 5 stranded copper conductor to BS EN 60228.
Fire Barrier : Mica glass tape.
Insulation : Thermoplastic compound of type TI 7 to EN 50363-7.
Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
COLOUR CODE:
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow.
PHYSICAL AND THERMAL PROPERTIES:
Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius :
OD<8mm : 4 × Overall Diameter
8mm≤OD≤12mm : 5 × Overall Diameter
OD>12mm : 6 × Overall Diameter
CONSTRUCTION PARAMETERS:
Conductor |
FFX100 07mZ1-U/R/K | ||||
---|---|---|---|---|---|
No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Min. Overall Diameter | Max. Overall Diameter | Approx. Weight |
No.×mm² | mm | mm | mm | kg/km | |
1×1.5 |
1 |
0.7 |
3.6 |
4.2 |
26 |
1×2.5 |
1 |
0.8 |
4.2 |
4.9 |
40 |
1×4 |
1 |
0.8 |
4.6 |
5.4 |
57 |
1×6 |
1 |
0.8 |
5.1 |
6.0 |
78 |
1×10 |
1 |
1.0 |
6.3 |
7.4 |
128 |
1×1.5 |
2 |
0.7 |
3.7 |
4.3 |
28 |
1×2.5 |
2 |
0.8 |
4.3 |
5.0 |
42 |
1×4 |
2 |
0.8 |
4.8 |
5.6 |
59 |
1×6 |
2 |
0.8 |
5.3 |
6.2 |
81 |
1×10 |
2 |
1.0 |
6.6 |
7.7 |
133 |
1×16 |
2 |
1.0 |
7.4 |
8.8 |
197 |
1×25 |
2 |
1.2 |
9.1 |
10.7 |
308 |
1×35 |
2 |
1.2 |
10.0 |
11.9 |
412 |
1×50 |
2 |
1.4 |
11.6 |
13.8 |
558 |
1×70 |
2 |
1.4 |
13.1 |
15.6 |
782 |
1×95 |
2 |
1.6 |
15.1 |
18.1 |
1078 |
1×120 |
2 |
1.6 |
16.6 |
19.8 |
1342 |
1×150 |
2 |
1.8 |
18.3 |
21.9 |
1650 |
1×185 |
2 |
2.0 |
20.3 |
24.3 |
2067 |
1×240 |
2 |
2.2 |
23 |
27.6 |
2703 |
1×300 |
2 |
2.4 |
25.5 |
30.6 |
3378 |
1×400 |
2 |
2.6 |
28.5 |
34.2 |
4267 |
1×500 |
2 |
2.8 |
31.5 |
37.9 |
5359 |
1×630 |
2 |
2.8 |
35 |
42.1 |
6884 |
1×1.5 |
5 |
0.7 |
3.8 |
4.4 |
27 |
1×2.5 |
5 |
0.8 |
4.4 |
5.1 |
42 |
1×4 |
5 |
0.8 |
4.9 |
5.8 |
59 |
1×6 |
5 |
0.8 |
5.4 |
6.3 |
81 |
1×10 |
5 |
1.0 |
6.7 |
7.8 |
134 |
1×16 |
5 |
1.0 |
7.7 |
9.1 |
197 |
1×25 |
5 |
1.2 |
9.4 |
11.2 |
304 |
1×35 |
5 |
1.2 |
10.7 |
12.7 |
410 |
1×50 |
5 |
1.4 |
12.5 |
14.9 |
585 |
1×70 |
5 |
1.4 |
14.2 |
17.0 |
811 |
1×95 |
5 |
1.6 |
16.1 |
19.2 |
1075 |
1×120 |
5 |
1.6 |
17.7 |
21.2 |
1341 |
1×150 |
5 |
1.8 |
19.6 |
23.5 |
1670 |
1×185 |
5 |
2.0 |
21.6 |
25.9 |
2042 |
1×240 |
5 |
2.2 |
24.5 |
29.4 |
2672 |
ELECTRICAL PROPERTIES:
Conductor operating temperature : 70°C
Ambient temperature : 30°C
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A
Conductor cross-sectional area |
Ref. Method A (enclosed in conduit in thermally insulating wall etc.) | Ref. Method B (enclosed in conduit on a wall or in trunking etc.) | Ref. Method C (clipped direct) | Ref. Method F (in free air or on a perforated cable tray horizontal or vertical) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Touching | Spaced by one diameter |
||||||||||
2 cables, single-phase a.c. or d.c. | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c. flat and touching | 3 or 4 cables, three-phase a.c. flat and touching or trefoil | 2 cables, single-phase a.c. or d.c. flat | 3 cables, three-phase a.c. flat | 3 cables, three-phase a.c. trefoil | 2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat | ||
Horizontal | Vertical | ||||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm² |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
14.5 |
13.5 |
17.5 |
15.5 |
20 |
18 |
- |
- |
- |
- |
- |
2.5 |
20 |
18 |
24 |
21 |
27 |
25 |
- |
- |
- |
- |
- |
4 |
26 |
24 |
32 |
28 |
37 |
33 |
- |
- |
- |
- |
- |
6 |
34 |
31 |
41 |
36 |
47 |
43 |
- |
- |
- |
- |
- |
10 |
46 |
42 |
57 |
50 |
65 |
59 |
- |
- |
- |
- |
- |
16 |
61 |
56 |
76 |
68 |
87 |
79 |
- |
- |
- |
- |
- |
25 |
80 |
73 |
101 |
89 |
114 |
104 |
131 |
114 |
110 |
146 |
130 |
35 |
99 |
89 |
125 |
110 |
141 |
129 |
162 |
143 |
137 |
181 |
162 |
50 |
119 |
108 |
151 |
134 |
182 |
167 |
196 |
174 |
167 |
219 |
197 |
70 |
151 |
136 |
192 |
171 |
234 |
214 |
251 |
225 |
216 |
281 |
254 |
95 |
182 |
164 |
232 |
207 |
284 |
261 |
304 |
275 |
264 |
341 |
311 |
120 |
210 |
188 |
269 |
239 |
330 |
303 |
352 |
321 |
308 |
396 |
362 |
150 |
240 |
216 |
300 |
262 |
381 |
349 |
406 |
372 |
356 |
456 |
419 |
185 |
273 |
245 |
341 |
296 |
436 |
400 |
463 |
427 |
409 |
521 |
480 |
240 |
321 |
286 |
400 |
346 |
515 |
472 |
546 |
507 |
485 |
615 |
569 |
300 |
367 |
328 |
458 |
394 |
594 |
545 |
629 |
587 |
561 |
709 |
659 |
400 |
- |
- |
546 |
467 |
694 |
634 |
754 |
689 |
656 |
852 |
795 |
500 |
- |
- |
626 |
533 |
792 |
723 |
868 |
789 |
749 |
982 |
920 |
630 |
- |
- |
720 |
611 |
904 |
826 |
1005 |
905 |
855 |
1138 |
1070 |
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B
Conductor cross-sectional area |
2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C & F(clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking) | Ref. Methods C & F (clipped direct, on trays or in free air) | |||||||||||||||||||
Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, Flat | Cables spaced*, Flat | ||||||||||||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
||||||||||||||
mm² |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|||||||||||||||
1.5 |
29 |
29 |
29 |
29 |
25 |
25 |
25 |
25 |
||||||||||||||
2.5 |
18 |
18 |
18 |
18 |
15 |
15 |
15 |
15 |
||||||||||||||
4 |
11 |
11 |
11 |
11 |
9.5 |
9.5 |
9,5 |
9.5 |
||||||||||||||
6 |
7.3 |
7.3 |
7.3 |
7.3 |
6.4 |
6.4 |
6.4 |
6.4 |
||||||||||||||
10 |
4.4 |
4.4 |
4.4 |
4.4 |
3.8 |
3.8 |
3.8 |
3.8 |
||||||||||||||
16 |
2.8 |
2.8 |
2.8 |
2.8 |
2.4 |
2.4 |
2.4 |
2.4 |
||||||||||||||
|
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
25 |
1.75 |
1.80 |
0.33 |
1.80 |
1.75 |
0.20 |
1.75 |
1.75 |
0.29 |
1.80 |
1.50 |
0.29 |
1.55 |
1.50 |
0.175 |
1.50 |
1.50 |
0.25 |
1.55 |
1.50 |
0.32 |
1.55 |
35 |
1.25 |
1.30 |
0.31 |
1.30 |
1.25 |
0.195 |
1.25 |
1.25 |
0.28 |
1.30 |
1.10 |
0.27 |
1.10 |
1.10 |
0.170 |
1.10 |
1.10 |
0.24 |
1.10 |
1.10 |
0.32 |
1.15 |
50 |
0.93 |
0.95 |
0.3 |
1.0 |
0.93 |
0.19 |
0.95 |
0.93 |
0.28 |
0.97 |
0.81 |
0.26 |
0.85 |
0.8 |
0.165 |
0.82 |
0.8 |
0.24 |
0.84 |
0.8 |
0.32 |
0.86 |
70 |
0.63 |
0.65 |
0.29 |
0.72 |
0.63 |
0.185 |
0.66 |
0.63 |
0.27 |
0.69 |
0.56 |
0.25 |
0.61 |
0.55 |
0.16 |
0.57 |
0.55 |
0.24 |
0.6 |
0.55 |
0.31 |
0.63 |
95 |
0.46 |
0.49 |
0.28 |
0.56 |
0.47 |
0.18 |
0.50 |
0.47 |
0.27 |
0.54 |
0.42 |
0.24 |
0.48 |
0.41 |
0.155 |
0.43 |
0.41 |
0.23 |
0.47 |
0.4 |
0.31 |
0.51 |
120 |
0.36 |
0.39 |
0.27 |
0.47 |
0.37 |
0.175 |
0.41 |
0.37 |
0.26 |
0.45 |
0.33 |
0.23 |
0.41 |
0.32 |
0.15 |
0.36 |
0.32 |
0.23 |
0.4 |
0.32 |
0.3 |
0.44 |
150 |
0.29 |
0.31 |
0.27 |
0.41 |
0.3 |
0.175 |
0.34 |
0.29 |
0.26 |
0.39 |
0.27 |
0.23 |
0.36 |
0.26 |
0.15 |
0.3 |
0.26 |
0.23 |
0.34 |
0.26 |
0.3 |
0.40 |
185 |
0.23 |
0.25 |
0.27 |
0.37 |
0.24 |
0.17 |
0.29 |
0.24 |
0.26 |
0.35 |
0.22 |
0.23 |
0.32 |
0.21 |
0.145 |
0.26 |
0.21 |
0.22 |
0.31 |
0.21 |
0.3 |
0.36 |
240 |
0.18 |
0.195 |
0.26 |
0.33 |
0.185 |
0.165 |
0.25 |
0.185 |
0.25 |
0.31 |
0.17 |
0.23 |
0.29 |
0.16 |
0.145 |
0.22 |
0.16 |
0.22 |
0.27 |
0.16 |
0.29 |
0.34 |
300 |
0.145 |
0.16 |
0.26 |
0.31 |
0.15 |
0.165 |
0.22 |
0.15 |
0.25 |
0.29 |
0.14 |
0.23 |
0.27 |
0.13 |
0.14 |
0.19 |
0.13 |
0.22 |
0.25 |
0.13 |
0.29 |
0.32 |
400 |
0.105 |
0.13 |
0.26 |
0.29 |
0.12 |
0.16 |
0.20 |
0.115 |
0.25 |
0.27 |
0.12 |
0.22 |
0.25 |
0.105 |
0.14 |
0.175 |
0.105 |
0.21 |
0.24 |
0.1 |
0.29 |
0.31 |
500 |
0.086 |
0.11 |
0.26 |
0.28 |
0.098 |
0.155 |
0.185 |
0.093 |
0.24 |
0.26 |
0.1 |
0.22 |
0.25 |
0.086 |
0.135 |
0.16 |
0.086 |
0.21 |
0.23 |
0.081 |
0.29 |
0.30 |
630 |
0.068 |
0.094 |
0.25 |
0.27 |
0.081 |
0.155 |
0.175 |
0.076 |
0.24 |
0.25 |
0.08 |
0.22 |
0.24 |
0.072 |
0.135 |
0.15 |
0.072 |
0.21 |
0.22 |
0.066 |
0.28 |
0.29 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance