Fire retardant cable(Fireguard)

300/500V PVC Insulated, Non-sheathed Power Cables (Single Core)

FGD100 05V-U/R/K (CU/PVC 300/500V Class 1/2/5)

BS Code: 2491X

HAR Code: H05V-U, H05V-R, H05V-K

 

 


APPLICATION:

This cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS:

Basic design to BS EN 50525-2-31(formerly BS 6004:2000)

FGD100 05V-U/R/K (CU/PVC 300/500V Class 1/2/5)

FIRE PERFORMANCE:

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2

VOLTAGE RATING:

300/500V

CABLE CONSTRUCTION:


Conductor

H05V-U

Class 1 solid copper conductor to BS EN 60228.

H05V-R

Class 2 stranded copper conductor to BS EN 60228.

H05V-K

Class 5 stranded copper conductor to BS EN 60228.

Insulation

PVC Type TI 1 according to BS EN 50363-3

COLOUR CODE:

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bicolours of any combination of the above mono-colours are permitted.

PHYSICAL AND THERMAL PROPERTIES:

Maximum temperature range during operation (PVC)

70°C

Maximum short circuit temperature (5 Seconds)

160°C

Minimum bending radius

Up to 8mm²:

4 x overall diameter

8mm² to 12mm²

5 x overall diameter

Above 12mm²

6 x overall diameter

CONSTRUCTION PARAMETERS:

Conductor FGD100 05V-U/R/K
No. of Cores x Cross Section Class of Conductor Nominal Insulation Thickness Maximum Overall Diameter Approx. Weight
No.xmm²   mm mm kg/km

1x0.50

1

0.6

2.3

8

1x0.75

1

0.6

2.5

11

1x1.0

1

0.6

2.7

14

1x0.50

2

0.6

2.4

9

1x0.75

2

0.6

2.6

12

1x1.0

2

0.6

2.8

14

1x0.50

5

0.6

2.5

8

1x0.75

5

0.6

2.7

11

1x1.0

5

0.6

2.8

13

ELECTRICAL PROPERTIES:

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A

Conductor cross-sectional area PVC insulated types (HD 21)
single-phase a.c. three-phase a.c.

mm²

A

A

0.50

3

3

0.75

6

6

1.0

10

10

Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.:
(i) When high ambient temperatures are involved, ie. above 30°C
(ii) Where long lengths are used
(iii) Where ventilation is restricted
(iv) Where the cords are used for other purposes, ego internal wiring of apparatus.

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B


Conductor cross-sectional area
d.c. or single-phase a.c. Three-phase a.c.
mm² mV/A/m mV/A/m

0.50

93

80

0.75

62

54

1.0

46

40