Fire retardant cable(Fireguard)
300/500V PVC Insulated, Non-sheathed Power Cables (Single Core 90°C)
FGD100 05V2-U/R/K (CU/PVC 300/500V Class 1/2/5)
BS Code : 2491XHR
HAR Code : H05V2-U, H05V2-R, H05V2-K
APPLICATION:
This cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS:
Basic design to BS EN 50525-2-31(formerly BS 6004:2000)
FIRE PERFORMANCE:
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2 |
---|
VOLTAGE RATING:
300/500V
CABLE CONSTRUCTION:
Conductor |
H05V-U |
Class 1 solid copper conductor to BS EN 60228. |
---|---|---|
H05V-R |
Class 2 stranded copper conductor to BS EN 60228. |
|
H05V-K |
Class 5 stranded copper conductor to BS EN 60228. |
|
Insulation | PVC Type TI 3 according to BS EN 50363-3 |
COLOUR CODE:
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bicolours of any
combination of the above mono-colours are permitted.
PHYSICAL AND THERMAL PROPERTIES:
Maximum temperature range during operation (PVC) | 90°C |
|
---|---|---|
Maximum short circuit temperature (5 Seconds) | 160°C |
|
Minimum bending radius | Up to 8mm² |
4 x overall diameter |
8mm² to 12mm² |
5 x overall diameter |
|
|
Above 12mm² |
6 x overall diameter |
CONSTRUCTION PARAMETERS:
Conductor | FGD100 05V-U/R/K | |||
---|---|---|---|---|
No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Maximum Overall Diameter | Approx. Weight |
No.xmm² | mm | mm | kg/km | |
1x0.50 |
1 |
0.6 |
2.3 |
8 |
1x0.75 |
1 |
0.6 |
2.5 |
11 |
1x1.0 |
1 |
0.6 |
2.7 |
14 |
1x0.50 |
2 |
0.6 |
2.4 |
9 |
1x0.75 |
2 |
0.6 |
2.6 |
12 |
1x1.0 |
2 |
0.6 |
2.8 |
14 |
1x0.50 |
5 |
0.6 |
2.5 |
8 |
1x0.75 |
5 |
0.6 |
2.7 |
11 |
1x1.0 |
5 |
0.6 |
2.8 |
13 |
ELECTRICAL PROPERTIES:
Current-Carrying Capacities (Amp) according to HD516 Table 7 (a)
Conductor cross-sectional area | PVC insulated types (HD 21) | |
---|---|---|
single-phase a.c. | three-phase a.c. | |
mm² |
A |
A |
0.50 |
3 |
3 |
0.75 |
6 |
6 |
1.0 |
10 |
10 |
Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.: |
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B
Nominal Cross Section Area |
2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||
---|---|---|---|---|---|---|---|---|
Ref. Methods A and B (enclosed in conduit or trunking) | Ref. Methods C, F & G (clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking | Ref. Methods C, F & G (clipped direct, on trays or in free air) | |||||
Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, Flat | Cables spaced*, Flat | ||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
0.50 |
93 |
93 |
93 |
93 |
80 |
80 |
80 |
80 |
0.75 |
62 |
62 |
62 |
62 |
54 |
54 |
54 |
54 |
1.0 |
46 |
46 |
46 |
46 |
40 |
40 |
40 |
40 |